Table 176: Option:
[0]
0-20 mA
[1]
4-20 mA
[2]
Digital Output
6-91 Terminal 42 Analog Output
Default value: [0] No operation
Parameter type: Option
2-setup: All setups
Conversion index: -
Data type: u_int8
Change during operation: True
Select the function of terminal 42 as an analog current output. See also
parameter 6-90 Terminal 42 Mode
.
Table 177: Option:
[0]
No operation
[100]
Output frequency
[101]
Reference
[102]
Feedback
[103]
Motor current
[106]
Power
[139]
Bus control
[184]
Mirror AI53 mA
[185]
Mirror AI54 mA
[254]
DC link voltage
6-92 Terminal 42 Digital Output
Default value: [0] No operation
Parameter type: Option
2-setup: All setups
Conversion index: -
Data type: u_int8
Change during operation: True
Select the function of terminal 42 as a digital current output. See also
parameter 6-90 Terminal 42 Mode
. See
parameter 5-40 Function
Relay
for description of the options.
Table 178: Option:
[0]
No operation
[1]
Control ready
[2]
Drive ready
[3]
Drive ready/remote control
[4]
Standby/no warning
[5]
Drive running
[6]
Running/no warning
[7]
Run in range/no warning
[8]
Run on ref/no warning
AU363928304090en-000101 / 130R0982
100 | Danfoss A/S © 2021.07
Parameters
VLT® Flow Drive FC 111
Programming Guide