[62]
Reset Counter
A
Input for reset of counter A.
[63]
Counter B (up)
Input for increment counting in the SLC counter.
[64]
Counter B
(down)
Input for decrement counting in the SLC counter.
[65]
Reset Counter B Input for reset of counter B.
[101] Sleep
A signal applied puts the drive into sleep mode.
[120] Lead Pump
Start
A signal applied puts the lead pump into start mode.
[121] Lead Pump Al-
ternation
A signal applied puts the lead pump into alternation mode.
[130] Pump 1 Inter-
lock
A signal applied puts the pump 1 into interlock mode.
[131] Pump 2 Inter-
lock
A signal applied puts the pump 2 into interlock mode.
[132] Pump 3 Inter-
lock
A signal applied puts the pump 3 into interlock mode.
[133] Pump 4 Inter-
lock
A signal applied puts the pump 4 into interlock mode.
[134] Pump 5 Inter-
lock
A signal applied puts the pump 5 into interlock mode.
[190] Fire Mode Ref
Bit 0
Enable a selection of 1 of the 8 fire mode references according to
.
[191] Fire Mode Ref
Bit 1
Enable a selection of 1 of the 8 fire mode references according to
.
[192] Fire Mode Ref
Bit 2
Enable a selection of 1 of the 8 fire mode references according to
.
5-11 Terminal 19 Digital Input
Default value: [0] No operation
Parameter type: Option
2-setup: All setups
Conversion index: -
Data type: u_int8
Change during operation: True
Parameter for configuring the input function on input terminal 19.
Table 135: Option:
[0]
No operation
No reaction to signals transmitted to the terminal.
[1]
Reset
Reset the after a trip/alarm. Trip lock alarms can be reset.
[2]
Coast inverse
Leave the motor in free mode. Logic 0
⇒
coast stop.
[3]
Coast and reset
inverse
Reset and coast stop inverted input (NC). Leaves the motor in free mode and resets the . Logic
0
⇒
coast stop and reset.
[4]
Quick stop in-
verse
Inverted input (NC). Generates a stop in accordance with the quick-stop ramp time set in
parameter
3-81 Quick Stop Ramp Time
. After ramping down, the shaft is in free mode.