16-27 Power Filtered [hp]
Default value: 0 hp
Parameter type: Range
2-setup: 1 setup
Conversion index: -3
Data type: int32
Change during operation: False
Motor power in hp. The value shown is calculated on the basis of actual motor voltage and motor current. The value is filtered, and a
few seconds may pass from when an input value changes to when the data read-out values change.
Table 313: Range:
Min: 0 hp
Max: 1000 hp
Default value: 0 hp
4.13.3 16-3* Drive Status
16-30 DC Link Voltage
Default value: 0 V
Parameter type: Range
2-setup: 1 setup
Conversion index: 0
Data type: u_int32
Change during operation: True
Show the actual DC-link voltage.
Table 314: Range:
Min: 0 V
Max: 65535 V
Default value: 0 V
16-34 Heatsink Temp.
Default value: 0°C
Parameter type: Range
2-setup: 1 setup
Conversion index: 0
Data type: int8
Change during operation: True
View the heat sink temperature of the drive.
Table 315: Range:
Min: -128°C
Max: 127°C
Default value: 0°C
16-35 Inverter Thermal
Default value: 0%
Parameter type: Range
2-setup: 1 setup
Conversion index: 0
Data type: u_int8
Change during operation: True
View the percentage of thermal load on the drive. At 100%, a trip occurs.
Table 316: Range:
Min: 0%
Max: 255%
Default value: 0%
16-36 Inv. Nom. Current
Default value: 0 A
Parameter type: Range
2-setup: 1 setup
Conversion index: -2
Data type: u_int16
Change during operation: True
View the inverter nominal current. The data is used for motor overload protection and so on.
Table 317: Range:
Min: 0 A
Max: 655.35 A
Default value: 0 A