Parameter
Option
Default
Usage
Parameter 3-41
Ramp 1 Ramp
Up Time
0.01–3600.00 s
Size related
If induction motor is selected, the ramp-up time is from 0 to
rated
parameter 1-23 Motor Frequency
. If PM motor is selec-
ted, the ramp-up time is from 0 to
parameter 1-25 Motor
Nominal Speed
.
Parameter 3-42
Ramp 1 Ramp
Down Time
0.01–3600.00 s
Size related
For induction motors, the ramp-down time is from rated
pa-
rameter 1-23 Motor Frequency
to
0
. For PM motors, the ramp-
down time is from
parameter 1-25 Motor Nominal Speed
to
0
.
Parameter 4-12
Motor Speed
Low Limit [Hz]
0.0–400.0 Hz
0 Hz
Enter the minimum limit for low speed.
Parameter 4-14
Motor Speed
High Limit [Hz]
0.0–400.0 Hz
100 Hz
Enter the maximum limit for high speed.
Parameter 4-19
Max Output
Frequency
0.0–400.0 Hz
100 Hz
Enter the maximum output frequency value. If
parameter
4-19 Max Output Frequency
is set lower than
parameter 4-14
Motor Speed High Limit [Hz]
,
parameter 4-14 Motor Speed High
Limit [Hz]
is set equal to
parameter 4-19 Max Output Frequen-
cy
automatically.
Parameter 5-40
Function Relay
See
parameter 5-40 Function
Relay
.
[9] Alarm
Select the function to control output relay 1.
Parameter 5-40
Function Relay
See
parameter 5-40 Function
Relay
.
[5] Drive run-
ning
Select the function to control output relay 2.
Parameter 6-10
Terminal 53
Low Voltage
0.00–10.00 V
0.07 V
Enter the voltage that corresponds to the low reference val-
ue.
Parameter 6-11
Terminal 53
High Voltage
0.00–10.00 V
10 V
Enter the voltage that corresponds to the high reference val-
ue.
Parameter 6-12
Terminal 53
Low Current
0.00–20.00 mA
4 mA
Enter the current that corresponds to the low reference val-
ue.
Parameter 6-13
Terminal 53
High Current
0.00–20.00 mA
20 mA
Enter the current that corresponds to the high reference val-
ue.
Parameter 6-19
Terminal 53
mode
[0] Current
[1] Voltage
[1] Voltage
Select if terminal 53 is used for current or voltage input.
Parameter
30-22 Locked
Rotor Detection
[0] Off
[1] On
[0] Off
–
Parameter
30-23 Locked
Rotor Detection
Time [s]
0.05–1 s
0.10 s
–
AU363928304090en-000101 / 130R0982
16 | Danfoss A/S © 2021.07
Programming
VLT® Flow Drive FC 111
Programming Guide