Set output speed used for registration of no-flow power at low speed.
Table 391: Range:
Min: 0 Hz
Max: 400 Hz
Default value: 0 Hz
22-34 Low Speed Power [kW]
Default value: 0 kW
Parameter type: Range
2-setup: All setups
Conversion index: -2
Data type: u_int32
Change during operation: True
Set no-flow power at low speed.
Table 392: Range:
Min: 0 kW
Max: 5.50 kW
Default value: 0 kW
22-37 High Speed [Hz]
Default value: 0 Hz
Parameter type: Range
2-setup: All setups
Conversion index: -1
Data type: u_int16
Change during operation: True
Set output speed used for registration of no-flow power at high speed.
Table 393: Range:
Min: 0 Hz
Max: 400 Hz
Default value: 0 Hz
22-38 High Speed Power [kW]
Default value: 0 kW
Parameter type: Range
2-setup: All setups
Conversion index: -2
Data type: u_int32
Change during operation: True
Set no-flow power at high speed.
Table 394: Range:
Min: 0 kW
Max: 5.50 kW
Default value: 0 kW
4.16.3.1 No-flow Power Tuning Sequence
N O T I C E
Set
parameter 1-03 Torque Characteristics
before tuning takes place.
Procedure
To stop flow, close the main valve.
Run with motor until the system has reached normal operating temperature.
Press the [Hand On] key on the LCP and adjust speed for approximately 85% of the rated speed. Note the exact speed.
Read power consumption either by looking for actual power in the data line in the LCP or call
parameter 16-10 Power [kW]
in
the Main Menu. Note the power readout.
Change speed to approximately 50% of the rated speed. Note the exact speed.
Read power consumption either by looking for actual power in the data line in the LCP or call
parameter 16-10 Power [kW]
in
the Main Menu. Note the power readout.
Program the speeds used in
parameter 22-33 Low Speed [Hz]
and
parameter 22-37 High Speed [Hz]
.
Program the associated power values in
parameter 22-34 Low Speed Power [kW]
and
parameter 22-38 High Speed Power [kW]
.
Switch back pressing [Auto On] or [Off].