Set a time constant for the current limit controller low-pass filter. A shorter period makes the control react faster to changes in cur-
rent.
Table 251: Range:
Min: 1 ms
Max: 100 ms
Default value: 26.0 ms
4.11.5 14-4* Energy Optimization
Parameters for adjusting the energy optimization level in both variable torque (VT) and automatic energy optimization (AEO) mode.
Automatic energy optimization is only active if
parameter 1-03 Torque Characteristics
is set to
[3] Auto Energy Optim
.
14-40 VT Level
Default value: 90%
Parameter type: Range
2-setup: All setups
Conversion index: 0
Data type: u_int8
Change during operation: False
Enter the level of motor magnetization at low speed. Low values reduce energy loss in the motor, but also reduce load capability.
Table 252: Range:
Min: 40%
Max: 90%
Default value: 90%
14-41 AEO Minimum Magnetisation
Default value: 66%
Parameter type: Range
2-setup: All setups
Conversion index: 0
Data type: u_int8
Change during operation: False
Enter the minimum allowable magnetization for AEO. Low values reduce energy loss in the motor, but also reduce resistance to
sudden load changes.
Table 253: Range:
Min: 40%
Max: 75%
Default value: 66%
14-44 d-axis current optimization for IPM
Default value: 100%
Parameter type: Range
2-setup: All setups
Conversion index: 0
Data type: u_int8
Change during operation: True
This parameter is available only when
parameter 1-10 Motor Construction
is set to
[2] PM, salient IPM, non-Sat
. Normally, VVC
+
PM
control automatically optimizes d-axis demagnetizing current based on d-axis and q-axis settings. When
parameter 1-10 Motor Con-
struction
is set to
[2] PM, salient IPM, non-Sat
, use this parameter to compensate the saturation effect at high load. Usually, decreas-
ing this value improves the efficiency. However, 0% means no optimization and the d-axis current is 0 (this is not recommended).
Table 254: Range:
Min: 0%
Max: 200%
Default value: 100%
4.11.6 14-5* Environment
These parameters help the drive to operate under special environmental conditions.
14-50 RFI Filter
Default value: [1] On
Parameter type: Option
2-setup: 1 setup
Conversion index: -
Data type: u_int8
Change during operation: False
This parameter is only valid for drives of the following enclosure sizes:
IP20, 3x380–480 V, enclosure sizes H6–H8.
AU363928304090en-000101 / 130R0982 | 135
Danfoss A/S © 2021.07
Parameters
VLT® Flow Drive FC 111
Programming Guide