User define 7
[88]
User define 8
[100]
[1605] Main actual value [N2]
4.9.4 8-5* Digital/Bus
Parameters for configuring the control word digital/bus merging.
8-50 Coasting Select
Default value: [3] Logic OR
Parameter type: Option
2-setup: All setups
Conversion index: -
Data type: u_int8
Change during operation: True
N O T I C E
This parameter is active only when
parameter 8-01 Control Site
is set to
[0] Digital and control word
.
Select control of the coasting function via the terminals (digital input) and/or via the bus.
Table 196: Option:
[0]
Digital input
Activate coast via a digital input.
[1]
Bus
Activate coast via the serial communication port.
[2]
Logic AND
Activate coast via the fieldbus/serial communication port, and via 1 of the digital inputs.
[3]
Logic OR
Activate coast via the serial communication port or via 1 of the digital inputs.
8-51 Quick Stop Select
Default value: [3] Logic OR
Parameter type: Option
2-setup: All setups
Conversion index: -
Data type: u_int8
Change during operation: True
N O T I C E
This parameter is active only when
parameter 8-01 Control Site
is set to
[0] Digital and control word
.
Select control of the quick stop function via the terminals (digital input) and/or via the bus.
Table 197: Option:
[0]
Digital input
Activate quick stop via a digital input.
[1]
Bus
Activate quick stop via the serial communication port.
[2]
Logic AND
Activate quick stop via the fieldbus/serial communication port, and via 1 of the digital inputs.
[3]
Logic OR
Activate quick stop via the serial communication port or via 1 of the digital inputs.
8-52 DC Brake Select
Default value: -
Parameter type: Option
2-setup: All setups
Conversion index: -
Data type: u_int8
Change during operation: True
N O T I C E
This parameter is active only when
parameter 8-01 Control Site
is set to
[0] Digital and control word
.
Select control of the DC brake function via the terminals (digital input) and/or via the bus.
AU363928304090en-000101 / 130R0982
110 | Danfoss A/S © 2021.07
Parameters
VLT® Flow Drive FC 111
Programming Guide