25-81 Pump Status
Default value: 0
Parameter type: Range
2-setup: All setups
Conversion index: 0
Data type: VisibleString
Change during operation: True
View the status for the pumps connected.
X=Disabled
O=Off
D=Speed controlled
R=Mains
Table 463: Range:
Min: 0
Max: 25
Default value: 0
25-82 Lead Pump
Default value: 0
Parameter type: Range
2-setup: All setups
Conversion index: 0
Data type: u_int8
Change during operation: True
View which pump is speed-controlled by the drive.
Table 464: Range:
Min: 0
Max: 5
Default value: 0
25-84 Pump ON Time
Default value: 0 h
Parameter type: Range
2-setup: 1 setup
Conversion index: 0
Data type: u_int32
Change during operation: True
View the total operating hours of the connected pumps. This parameter can be reset to 0.
Table 465: Range:
Min: 0 h
Max: 2147483647 h
Default value: 0 h
4.19.6 25-9* Service
Parameters for service use.
25-90 Pump Interlock
Default value: [0] Off
Parameter type: Option
2-setup: All setups
Conversion index: -
Data type: u_int8
Change during operation: True
Choose the pump to interlock for, for example, service. The pump will be taken out of any pump cycling, and more.
Table 466: Option:
[0]
Off
[1]
On