Table 34: Range:
Min: 0
Max: 999
Default value: 0
0-61 Access to Main Menu w/o Password
Default value: [0] Full access
Parameter type: Option
2-setup: 1 setup
Conversion index: -
Data type: u_int8
Change during operation: True
Table 35: Option:
[0] Full access
Disable the password defined in
parameter 0-60 Main Menu Password
.
[1] LCP: Read only Prevent unauthorized editing of Main Menu parameters.
[2] LCP: No access Prevent unauthorized viewing and editing of Main Menu parameters.
[3] Bus: Read only Provide read-only access to parameters via fieldbus.
[5] All: Read only
Prevent unauthorized editing of main menu parameters and provides read-only access to parameters via
fieldbus.
4.3 Parameter Group 1-** Load and Motor
Parameters related to the motor nameplate load compensations and application load type.
4.3.1 1-0* General Settings
Define whether the drive operates in speed mode or torque mode; and whether the internal PID control should be active or not.
1-00 Configuration Mode
Default value: [0] Open Loop
Parameter type: Option
2-setup: All setups
Conversion index: -
Data type: u_int8
Change during operation: True
Select the application control principle to be used.
Table 36: Option:
[0] Open
Loop
Motor speed is determined by applying a speed reference or by setting the wanted speed when in hand-on
mode. Open loop is also used if the drive is part of a closed-loop control system based on an external PI con-
troller providing a speed reference signal as output.
[3] Process
Closed
Loop
N O T I C E
When set for closed loop, the commands
Reversing
and
Start Reversing
do not reverse the direction of the
motor.
A reference from the built-in PI controller determines the motor speed. The built-in PI controller varies the mo-
tor speed as of a closed-loop control process (for example, constant pressure or flow). Configure the PI control-
ler in
parameter group 20-** Drive Closed Loop
.
1-01 Motor Control Principle
Default value: [1] VVC
+
Parameter type: Option
2-setup: All setups
Conversion index: -
Data type: u_int8
Change during operation: False
Select U/f mode or VVC
+