5.5.36 WARNING/ALARM 92, No Flow
Cause
A no-flow condition has been detected in the system.
Parameter 22-23 No-Flow Function
is set for alarm.
Troubleshooting
Troubleshoot the system and reset the drive after the fault has been cleared.
5.5.37 WARNING/ALARM 93, Dry Pump
A no-flow condition in the system with the drive operating at high speed may indicate a dry pump.
Parameter 22-26 Dry Pump Func-
tion
is set for warning or alarm.
Troubleshooting
Troubleshoot the system.
Reset the drive when the fault is cleared.
5.5.38 WARNING/ALARM 94, End of Curve
Feedback is lower than the set point. This may indicate a leakage in the system.
Parameter 22-50 End of Curve Function
is set for
warning or alarm.
Troubleshooting
Troubleshoot the system.
Reset the drive when the fault is cleared.
5.5.39 WARNING/ALARM 95, Broken Belt
Cause
Torque is below the torque level set for no load, indicating a broken belt. See
parameter group 22-6* Broken Belt Detection
.
Troubleshooting
Troubleshoot the system.
Reset the drive after the fault is cleared.
5.5.40 ALARM 99, Locked Rotor
Cause
The rotor is blocked.
For 18–30 kW: If the protection is triggered more than 10 repeated times, auto reset transitions to require a manual operation to
clear the alarm.
Troubleshooting
Ensure that the rotor can operate freely.
Check the settings in
parameter group 1-1* Motor Selection
.
Check the settings in
parameter group 1-2* Motor Data
.
5.5.41 ALARM 101, Flow/pressure Info Missing
Cause
Sensorless-pump table is missing or wrong.
Troubleshooting
Download sensorless-pump table again.
5.5.42 ALARM 126, Motor Rotating
Cause
High back-EMF voltage.
Troubleshooting
Stop the rotor of the PM motor.