Outline of Functions (Outdoor unit)
SiBE811001EB
85
CONVENI-PACK
(4) Capacity control
Capacity control for freezing
Capacity control for air conditioning
0.6762 MPa
E
0.6468 MPa
D
&
OR
&
OR
&
&
Capacity
control
• Increases/decreases compressor frequency with low pressure made into control volume to obtain optimum cooling
capacity for the target evaporating temperature (Tst). The target evaporating temperature, Tst becomes the value set
by DIP switch, button-switch, etc. (Please refer to "Field setting")
Increasing/Decreasing of frequency is conducted by 1 step increments every 30 seconds. However, operation
becomes thermostat ON/OFF at low load. Lpm = Min (Lpm_x, f(Ta) (Caution! Ensure the target evaporating
temperature does not exceed the outdoor air temperature. In addition, the lower limit of Lpm is 0.29MPa, (-20˚C).
• Controls the number of compressor units on the air conditioning at cooling
Freezing
capacity
DOWN
Keep
freezing
capacity
2 air conditioning
units operate
1 air conditioning
unit operates
-0.0147MPa
≤
Lpm
≤
0.0147MPa
• INV_STEP > 1
• Lpm < -0.0147MPa
• Operation mode: 6, 7, 8, 11, 12, 24
• LP2 > E MPa continues for consecutive 3 minutes or more
• Capacity of the AC indoor unit while thermostat ON
≥
7HP
• LP2 < 0.3626MPa
• Capacity of the AC indoor unit while thermostat ON < 7 HP
• Operation mode: 5, 17
• LP2 < D MPa continues for consecutive 8 minutes or more
• Operation mode: 5, 17
&
OR
• INV_STEP < 20
• Lpm > 0.0147MPa
Freezing
capacity
UP
-0.0147MPa
≤
Lpm
≤
0.0147MPa
• Lpm: LP1 - Lpm
• Ta: Outdoor air temperature
• f(Ta): Equivalent saturation pressure by
outdoor air temperature
Lpm_x = f(Tst): Saturation pressure corresponding to target evaporating temperature
<When the number of compressors
remains unchanged>
• Reduce the speed of the compressor
with 1 step (for every 30 seconds).
<When the number of compressors
goes from 1 unit to 2 units>
<When the number of compressors
remains unchanged>
• Increase the compressor speed with
1 step (every 30 seconds).
&
• f( Lpm) > 3˚C
• HP < HPn - 0.098MPa or 2.94MPa
• Increase the compressor speed with
3 step.
OR
<When the number of compressors
goes from 2 units to 1 unit>
• INV_STEP
≤
1
• Lpm < -0.0147MPa continues for
consecutive 5 minutes or more
• Lpm < -0.0294MPa continues for
consecutive 1 minute or more
• Lpm < -0.0392MPa
• Successful condition formation of
the high pressure ratio.
• INV_STEP
≤
1
• Lpm > 0.0147MPa continues for
consecutive 10 minutes or more
• Lpm > 0.0294MPa continues for
consecutive 1 minute or more
• Lpm > 0.049MPa
• Successful condition formation of
roll over difference pressure.
• Reduce the speed of the compressor
with 3 step.
• Lpm < -0.074MPa