SiBE811001EB
Test Operation
CONVENI-PACK
70
5.
Check the sealing condition through the sight glass of the outdoor unit. In case of shortage
of refrigerant, check if the refrigerant is charged to the specified level.
6.
Check the following on each unit.
7.
Be sure to turn OFF the operation switch before turning OFF the power.
Error diagnosis
Check the following if nothing is displayed on the remote controller during the test operation.
<Indoor unit (air-conditioner)>
1. Is the power turned ON?
2. Is the wire broken or incorrectly wired (between the power, the indoor unit and the remote
controller)?
3. Has the fuse on PCB melted?
Take the following action if you find an error code on the remote controller during the test
operation.
∗
1
Set the operating switch to the “OFF” position to reset the power supply and then return the
switch to the “ON” position to restart the unit. If the problem persists, refer to the Service Manual.
If you have changed the power wire and the transmission line, keep the power of the indoor
unit (air-conditioner, refrigeration showcase, refrigeration unit cooler) and the integrated heat
control board turned ON, turn OFF the operation switch of the outdoor units and never fail to
press the BS button (BS5) on PCB (A1P) in the electric accessory box (right) of the outdoor
unit for at least 10 seconds (Open the inspection door (right) on the upper right portion of the
electric accessory box and operate the BS button (BS5) using an insulating rod). (See the
right figure.)
Refer to the Service Manual for other error codes.
Caution
Do not disconnect the power supply for 1 minute after setting the operating switch to “ON”.
Electric leak detection is performed for several seconds after the operating switch is set to
“ON” and each compressor starts operating, so disconnecting the power supply during that
time will result in a false detection.
Refrigeration showcase
Cold air should be blowing and the temperature should decrease to the
preset level.
The electronic expansion valve should be controlled on an appropriate
superheated degree.
The unit should start defrosting operation by the time set on the timer.
Refrigeration unit cooler
Cold air should be blowing and the temperature should decrease to the
preset level.
The electronic expansion valve should be controlled on an appropriate
superheated degree.
The unit should start defrosting operation by the time set on the timer.
Air-conditioner
Cold air (or hot air) should be blowing.
Error code
Defect at installation
Action to be taken
E3, E4
Stop valves closed
Fully open the stop valves.
L4
The air passage is blocked.
Remove obstacles blocking the air
passage.
U1
Reverse-phase of the power supply
Exchange 2 wires out of 3 power
supply wires.
U2
Voltage drop
Check the voltage drop.
U4, UF
Wrong wiring of transmission lines
between units
Check the connection of transmission
lines between the outdoor unit and the
air-conditioner.
UA
In the case of system discrepancy
Check if the air-conditioner is
connected as should be assembled.
E2
Electric leak
See
∗
1.
Inspection door (right)
(Upper right portion of the electric accessory box)