SiBE811001EB
Troubleshooting
CONVENI-PACK
214
Troubleshooting
∗
1.Check the procedure for fan motor connector
(1) Power OFF the fan motor.
(2) Remove the connector (X2A or X4A) on the PCB to measure the following resistance value.
Judgement criteria: resistance value between each phase is within ±20%
Connect correctly.
NO
Replace the fan motor.
NO
Replace the inverter PCB.
z
For fan motor 1: replace the
inverter PCB (A5P)
z
For fan motor 2: replace the
fan inverter PCB (A9P)
YES
Caution
Be sure to turn off the power switch before connecting or disconnecting connectors, or parts may be damaged.
Cut the power supply OFF.
Check the fan motor corresponding to
the error code “
H7
” in the monitor
mode.
Check the connector of the fan motor
(
∗
1).
YES
Check if signal wire
connector for the
corresponding fan
motor is normal.
Check if the
resistance of the fan
motor lead wire
between Vcc and
UVW and between
GND and UVW are
balanced.
Connector for signal wires
(X2A or X4A)
X2A
5 Gray
4 Pink
3 Orange
2 Blue
1 Yellow
5 Gray
GND
Vcc
W
V
U
Measure the
resistance
between Vcc-
UVW and
GND-UVW.
Measure the
resistance
between Vcc-
UVW and
GND-UVW.