Troubleshooting
SiBE811001EB
257
CONVENI-PACK
8.5.5 Inverter Compressor Motor Lock
Error Code
E5
Applicable
Models
LCBKQ3AV1
Method of Error
Detection
Inverter PCB takes the position signal from UVW line connected between the inverter and
compressor, and the error is detected when any abnormality is observed in the phase-current
waveform.
Error Decision
Conditions
This error will be output when the inverter compressor motor does not start up even in forced
startup mode.
Supposed
Causes
Inverter compressor lock
High differential pressure (0.5MPa or more)
Incorrect UVW wiring
Stop valve is not opened
Slugging state of refrigerant (Leakage of electronic expansion valve, defective electronic
expansion valve in showcase and leakage of liquid solenoid valve)
Too frequent ON/OFF operation due to insufficient loading
Oil not returned due to defective onsite piping work
LED Indications
First digit
l h k h h l l
Second digit
l k h h l h l