Troubleshooting
SiBE811001EB
249
CONVENI-PACK
8.4.59 System is not Set yet
Error Code
UF
Applicable
Models
All indoor models
LRYEQ16AY1
Method of Error
Detection
Error is detected by wiring check operation.
Error Decision
Conditions
The number of indoor units in terms of transmission is not corresponding to that of indoor units
that have made changes in temperature.
Supposed
Causes
Improper connection of transmission wiring between indoor-outdoor units and outdoor-
outdoor units
Failure to execute check operation
Defective indoor unit PCB
Stop valve is not opened
Troubleshooting
Note:
Wiring check operation may not be successful if carried out after the outdoor unit has been OFF for more than
12 hours, or if it is not carried out after running all connected indoor units in the fan mode for at least an hour.
Are the stop valves
opened?
NO
Open the stop valve.
Caution
Be sure to turn off the power switch before connecting or disconnecting connectors, or parts may be damaged.
YES
Is the check operation
carried out?
Is indoor - outdoor
and outdoor - outdoor
unit transmission
wiring normal?
Is indoor-outdoor
and outdoor-outdoor
unit transmission
wiring normal?
NO
Replace the indoor unit PCB.
NO
After fixing the incorrect wiring,
press and hold the RESET
button on the master outdoor
unit PCB for 5 seconds.
∗
The unit will not run for up to
12 minutes.
YES
Wiring check operation may not
have been carried out
successfully.
YES
YES
NO