Field Setting
SiBE811001EB
113
CONVENI-PACK
(12) Output Method of Caution Output During Communication Box Connection
Setting an address of the outdoor unit is required to connect to the communication box (BRR9A1V1).
When an address of the outdoor unit is set, the Caution output does not work.
(Warning output can be output even during communication box connection)
The following setting is required to output Caution output during communication box connection.
The number "07" in the "No." column represents the number of times to press the BS2 button.
(13) H/P mode prohibition setting details
(However, driving modes 40, 41, and 42 are not prohibited in consideration of the load of the showcase there. )
No.
Display of setting items
Display of setting conditions
Setting item
H1P H2P H3P H4P H5P H6P H7P
3-07
Back-up output setting when
AIRNET is set
Output method of Caution output
during communication box
connection
k
h
h
h
k
k
k
(
)
H1P H2P H3P H4P H5P H6P H7P
No output (Factory setting)
k
h
h
h
h
h
k
Output
k
h
h
h
h
k
h
YES
NO
OR
&
&
YES
NO
YES
NO
H/P mode prohibition
• Setting mode: (2 - 15): Set = 1
• Max(Tset)
≤
16˚C +: Setting mode (2 - 17)
Tset: Remote control preset temperature
Tr: Inhalation temperature
• Min(Tset - Tr) < 4˚C + Setting mode (2 - 38)
• Everything passes continuous 3 hours
or more by numbers except 43, 46, 47,
52, and 59 mode of operation.
• Min(Tset - Tr)
≤
2˚C + Setting mode (2 - 38)
H/P.(43, 46, 47, 52, and 59 mode)
mode is prohibited
RETURN
H/P (43, 46, 47, 52, and 59 mode)
mode is permitted.
Min(Tset - Tr)
≥
6˚C
+ Setting mode (2 - 38)
H/P (43, 46, 47, 52, and 59 mode)
mode is permitted.