Field Setting
SiBE811001EB
115
CONVENI-PACK
< Heating reinforced relation (Partial H/R mode) >
k
Heating capacity UP condition
When condition is the same as above
→
Shift the four way valve-B to be OFF (100 % Heat Recovery operation mode)
< Heating reinforced relation (H/P assistance number standby time)>
Prevention of decrease in integration heating capacity because of compressor driving/stop of transition with hunting
cap of high pressure
• HP < f(f (Target Tc)–0.294MPa
• Ta < 25˚C
• Min(Tr) < 25˚C + Setting mode: (2 - 42)
• Min(Tset-Tr) > 3˚C(1˚C is subtracted every 5 minutes.)
• Max(Tset-Tr) > 7˚C(1˚C is subtracted every 5 minutes.)
• Min(Tset-Tr) > 1˚C + Setting mode :(3 - 58) ˚C(Factory setting: 0˚C) + Setting mode: (3 - 61) ˚C(Factory setting: 4˚C)
• Max(Tset-Tr) > 1˚C + Setting mode :(3 - 59) ˚C(Factory setting: 0˚C) + Setting mode: (3 - 63) ˚C(Factory setting: 8˚C)
• It is the batch heating strengthening set (sub-DIP SW2 - 2 = ON)
OR
&
• Operation mode = 41,42 continuous setting mode: (3 - 56)minute
• It is the batch heating strengthening set (sub-DIP SW2 - 2 = OFF)
• It is the batch heating strengthening set (sub-DIP SW2 - 2 = ON)
OR &