Field Setting
SiBE811001EB
119
CONVENI-PACK
These numbers represent the number of times to press the BS2 button to select each setting.
No.
Display of setting items
Display of setting conditions
Setting item
H1P H2P H3P H4P H5P H6P H7P
42
Absorption temperature degree
correction at heating capacity UP of
partial heat recovery
Purpose)
It uses it for the adjustment when the
heating capacity is started.
Refer to details to another page.
k
k
h
k
h
k
h
43 STD1 compressor forced OFF
k
k
h
k
h
k
k
The compressor forced stop setting does not turn off even if the power is recycled.
44 STD2 compressor forced OFF
k
k
h
k
k
h
h
The compressor forced stop setting does not turn off even if the power is recycled.
57
Setting of defrost timer at the time of
ambient temperature -5°C or more
Purpose)
It uses it as an adjustment at defrost
intervals.
Factory set: None
Refer to details to another page.
k
k
k
k
h
h
k
59
Setting of defrost timer at the time of
less than -5°C in ambient temperature
Purpose)
It uses it as an adjustment at defrost
intervals.
Factory set: 6hr
Refer to details to another page.
k
k
k
k
h
k
k
61
Capacity DOWN extension by suction
temperatures fluctuate of heating
capacity
Purpose)
It uses it to adjust improvement/down
of the heating capacity.
Refer to details to another page.
k
k
k
k
k
h
k
63
Heating capacity _ Thermo. ON
number correction
Purpose)
It uses it to adjust improvement/down
of the heating capacity.
Refer to details to another page.
k
k
k
k
k
k
k
Correction
temperature
H1P H2P H3P H4P H5P H6P H7P
Set 0
(factory setting)
0°C
k
h
h
h
h
h
h
Set 1
-2°C
k
h
h
h
h
h
k
Set 2
-1°C
k
h
h
h
h
k
h
Set 3
1°C
k
h
h
h
h
k
k
Set 4
2°C
k
h
h
h
k
h
h
Set 5
3°C
k
h
h
h
k
h
k
Set 6
4°C
k
h
h
h
k
k
h
Set 7
5°C
k
h
h
h
k
k
k
Set 8
6°C
k
h
h
k
h
h
h
Set 9
7°C
k
h
h
k
h
h
k
H1P H2P H3P H4P H5P H6P H7P
Normal control (factory setting)
k
h
h
h
h
h
k
STD1 compressor forced OFF
k
h
h
h
h
k
h
H1P H2P H3P H4P H5P H6P H7P
Normal control (factory setting)
k
h
h
h
h
h
k
STD2 compressor forced OFF
k
h
h
h
h
k
h
Defrost timer by
ambient
temperature
(more –5°C)
H1P H2P H3P H4P H5P H6P H7P
Set 0
(Factory set)
None
k
h
h
h
h
h
h
Set 1
1hr
k
h
h
h
h
h
k
Set 2
2hr
k
h
h
h
h
k
h
Set 3
4hr
k
h
h
h
h
k
k
Set 4
6hr
k
h
h
h
k
h
h
Set 5
8hr
k
h
h
h
k
h
k
Set 6
12hr
k
h
h
h
k
k
h
Defrost timer by
ambient
temperature
(more –5°C)
H1P H2P H3P H4P H5P H6P H7P
Set 0
(Factory set)
6hr
k
h
h
h
h
h
h
Set 1
1hr
k
h
h
h
h
h
k
Set 2
2hr
k
h
h
h
h
k
h
Set 3
4hr
k
h
h
h
h
k
k
Set 4
8hr
k
h
h
h
k
h
h
Set 5
12hr
k
h
h
h
k
h
k
Set 6
None
k
h
h
h
k
k
h
Room temperature
pendency
H1P H2P H3P H4P H5P H6P H7P
Set 0
(factory setting)
It is.
k
h
h
h
h
h
k
Set 1
None
k
h
h
h
h
k
h
Heating
capacity_Thermo
ON number
correction
H1P H2P H3P H4P H5P H6P H7P
Set 0
(factory setting)
0
k
h
h
h
h
h
k
Set 1
-2
k
h
h
h
h
k
h
Set 2
-1
k
h
h
h
k
h
h
Set 3
1
k
h
h
k
h
h
h
Set 4
2
k
h
k
h
h
h
h
Set 5
There is no
limitation.
k
k
h
h
h
h
h