Troubleshooting
SiBE811001EB
199
CONVENI-PACK
Troubleshooting
Check in the monitor mode
Check the connection status of the connectors
Models have 2 fans.
Check electric motor (electric motor 1 or 2) corresponding to error
code “
E7
” in the monitor mode of outdoor unit PCB.
k
Fan motor 1: relay connector or X1A, X2A of fan inverter PCB (A5P).
k
Fan motor 2: relay connector or X1A, X2A of fan inverter PCB (A9P).
Check the color of relay connectors
k
Fan motor 1: Both power supply wire and signal wire are all white.
k
Fan motor 2: Both power supply wire and signal wire are red in the
PCB side and white in the motor side.
NO
NO
Cut the power supply OFF and wait for 10 minutes.
Check if any
foreign substances
around the fan.
Check if any
connector is
disconnected.
Relay connectors have
any connection error.
A
Remove the foreign substances.
YES
Insert the connector.
YES
Correct the connection of the
relay connectors.
YES
Caution
Be sure to turn off the power switch before connecting or disconnecting connectors, or parts may be damaged.
NO