Troubleshooting
SiBE811001EB
237
CONVENI-PACK
8.4.50 Power Supply Insufficient or Instantaneous Failure
Error Code
U2
Applicable
Models
LRYEQ16AY1
Method of Error
Detection
Detection of voltage of main circuit capacitor built in the inverter and power supply voltage.
Error Decision
Conditions
When the voltage aforementioned is less than 190V
Supposed
Causes
Power supply insufficient
Instantaneous power failure
Open phase
Defective inverter PCB
Defective outdoor control PCB
Defective compressor
Defective main circuit wiring
Defective fan motor
Defective connection of signal cable
Troubleshooting
There are problems
on the condition of
power supply
described above.
The insulation resistance
of compressor is not more
100k
Ω
.
The insulation
resistance of fan motor
is not more 1M
Ω.
Check the condition of the power
supply.
Check if power supply voltage is
200V
±
10%.
Check if there is open phase or
defective wiring.
Check if power supply voltage side
unbalance is within 6V.
NO
NO
NO
A
Correct the fault.
YES
Replace the compressor.
YES
Replace the fan motor.
∗
If the fan motor is badly
damaged, replace the
fan PCB (A5P or A9P).
YES
Caution
Be sure to turn off the power switch before connecting or disconnecting connectors, or parts may be damaged.