Troubleshooting
SiBE811001EB
299
CONVENI-PACK
[Cleaning_function]
[Amp/Fin]
How to observe booster information using the outdoor ram monitor
It is possible to observe booster information from the outdoor ram monitor.
Note:
When the booster temperature display is in the negative, the value displayed is the
temperature value plus an additional 128.
Data renewal time is in approximately 20 seconds intervals.
To see booster information using the outdoor ram monitor, refer to the following steps 1 to 7 that are outlined below.
(1) While taking note of the "QupBu_judge" as shown below, record the values (0 to 9) beside bit "5".
∗
The below screen is the outdoor ram monitor model screen.
(2) Close all ram monitors currently open.
During_cleaning
When the outdoor unit is receiving indoor cleaning request (0/1)
Indoor_unit_cleaning_demand
Cleaning request from the indoor unit (0/1)
Indoor_unit_During_cleaning
During cleaning of the indoor unit (0/1)
Total_Amp
Total current value of the outdoor unit
Inv_1_Amp
INV. primary current value
Inv_2_Amp
INV. secondary current value
NON1_Amp
STD1 current value
NON2_Amp
STD2 current value
Fin_Temp
Fin temperature
Fan1_1_Amp
Fan1_primary current
Fan1_2_Amp
Fan1_secondary current
Fan2_1_Amp
Fan2_primary current
Fan2_2_Amp
Fan2_secondary current
Example:
As shown in the figure to the left,
enter "3" where bit "5" appears.