8.4.26 Transmission Error between Outdoor unit and Booster Unit
Error Code
EH
Applicable
Models
LRYEQ16AY1
LCBKQ3AV1
Method of Error
Detection
Check if the transmission between outdoor unit and booster unit is correctly executed using
micro-computer.
Error Decision
Conditions
When transmission is not carried out normally for a certain amount of time
Supposed
Causes
Outdoor unit to booster unit transmission wiring F1, F2 disconnection, short circuit or wrong
wiring
Booster unit power supply is OFF
Troubleshooting
The booster’s power supply
was turned “OFF”
Transmission
wire between outdoor unit and
booster unit is break.
Restore the transmission wire.
YES
Turn ON the power supply for
the booster unit.
Replace the outdoor unit PCB
or booster unit PCB.
YES
NO
NO
Caution