8.4.19 High Pressure Switch Abnormality
Error Code
E3
Applicable
Models
LRYEQ16AY1
Method of Error
Detection
Abnormality is detected when the contact of the high pressure protection switch opens.
Error Decision
Conditions
Error is generated when the high pressure switch activation count reaches the number specific
to the operation mode.
(Reference) Operating pressure of high pressure switch
Operating pressure: 3.8MPa
Reset pressure:
2.85MPa
Supposed
Causes
Actuation of outdoor unit high pressure switch
Defective high pressure switch
Defective outdoor unit main PCB (A1P), sub PCB (A2P)
Instantaneous power failure
Defective high pressure sensor
Troubleshooting
Are the 3 points above
OK?
(1) Mount a pressure gauge on the high pressure service port.
(2) Reset the operation using the remote controller, and then restart the
operation.
YES
Replace the high pressure
switch.
NO
Rectify the defective points, if
any.
NO
Replace the high pressure
sensor.
NO
Caution
Be sure to turn off the power switch before connecting or disconnecting connectors, or parts may be damaged.
Check for the points shown below.
(1) Is the stop valve open?
(2) Is the high pressure switch connector properly connected to the outdoor
unit main PCB?
(3) Does the high pressure switch have continuity?
Does the stop due
to error (
E3
) recur?
Are the
characteristics of the
high pressure sensor
normal? (See
∗
1.)
Is the high pressure
switch operating value
normal (i.e., 3.8MPa)?
YES
YES
NO
YES
A