Test Operation
SiBE811001EB
67
CONVENI-PACK
5.6
Checks after Work Completion
Make sure the following works are complete in accordance with the installation manual.
• Piping work
• Wiring work
• Air tight test/Vacuum drying
• Installation work for indoor unit
• Installation work for booster unit
(In case of the booster unit connection)
5.7
Additional Refrigerant Charge
For refrigerant filling contractor
Use R-410A for refrigerant replenishment.
The R-410A refrigerant cylinder is painted with a pink belt.
Warning
Electric Shock Warning
Securely close the control box lid before turning power ON.
Before turning power ON, check through the inspection hole (on the left-hand side) of the
control box lid that the RUN switch is set to OFF.
If the RUN switch is set to ON, the fan may rotate.
Use an insulated rod to operate the press buttons via the inspection door of EL. COMPO.
BOX.
There is a risk of electric shock if you touch any live parts, since this operation must be
performed with the power ON.
Check the LED indicators on the PCB (A1P) of the outdoor unit through the inspection hole
(on the right-hand side) of the control box lid after the outdoor unit is turned ON (see the
illustration).
(The compressor will not operate for approximately 10 minutes after the outdoor unit and air
conditioning indoor unit are turned ON.
H2P will be turned OFF when in a condition to be able to operate a system. (H3P continues
blinking state)
Warning
Use protective gear (e.g., protective gloves and glasses) at the time of refrigerant filling.
Pay attention to the rotation of the fan whenever the front panel is opened while working.
The fan can rotate continuously for a while after the outdoor unit stops operating.
Control box
Control box lid
REMOTE OFF
ON
Inspection hole
(left-hand side)
Inspection hole
(right-hand side)
Inspection
hole cover
Lift up this tab and
open the cover.
LED
(H1~8P)
Inspection hole (right-hand side)
(upper right-hand side of control box)
RUN switch
(factory setting: OFF)
Inspection hole (left-hand side)
(upper left-hand side of control box)