Troubleshooting
SiBE811001EB
265
CONVENI-PACK
8.5.11 Inverter PCB Abnormality
Error Code
L1
Applicable
Models
LCBKQ3AV1
Method of Error
Detection
Error is detected based on the current value during waveform output before starting
compressor.
Error is detected based on the value from current sensor during synchronous operation when
starting the unit.
Error Decision
Conditions
Overcurrent (OCP) flows during waveform output.
Error of current sensor during synchronous operation.
IGBT failure.
Supposed
Causes
PCB (A1P)
z
IPM (
∗
1) failure
z
Current sensor failure
z
Defective IGBT or drive circuit
Troubleshooting
Note:
∗
1. IPM: IPM is a semiconductor device for electric power incorporating the drive circuit and
self-protection feature of the power device which controls electric power.
LED Indications
First digit
l h k h l l l
Second digit
l k h h h h l
Turn OFF the power supply once,
and then turn ON the power supply
again.
Does the power
supply normally
restart?
It is supposed that the defective
results from external causes
other than failures (e.g.
exogenous noises or thunder).
YES
Replace the inverter PCB.
NO
Caution
Be sure to turn off the power switch before connecting or disconnecting connectors, or parts may be damaged.