Troubleshooting
SiBE811001EB
195
CONVENI-PACK
Troubleshooting
∗
1. Make a comparison between the voltage of the pressure sensor and that read by the pressure gauge.
(As to the voltage of the pressure sensor, make measurement of voltage at the connector, and then convert it to pressure
according to information on P.295.)
∗
2. Make measurement of voltage of the pressure sensor.
Refer to P.286, 287.
Is the stop valve open?
Are the
characteristics of
the low pressure
sensor normal?
(See
∗
1.)
Check if the “low
pressure” value and the
actual measurement
value by pressure
sensor are the same.
Open the stop valve.
NO
Replace the low pressure
sensor.
NO
Replace the outdoor unit main
PCB (A1P).
NO
Caution
Be sure to turn off the power switch before connecting or disconnecting connectors, or parts may be damaged.
YES
YES
YES
(1) Mount a pressure gauge on the low
pressure service port.
(2) Reset the operation using the
remote controller, and then restart
the operation.
Service Checker
Connect the service checker to compare the “low pressure” value and
the actual measurement value by pressure sensor (Refer to
∗
1) by
using the service checker.
· The low pressure sensor is normal, and the pressure detected with
the PCB is also normal.
· The low pressure has really become low.
CHECK 2-1, 2-2
Referring to information on P.286, remove the
causes by which the low pressure has become low.
+5V
Connector for low pressure sensor
Micro-computer
A/D input
Make measurement of DC voltage between these wires.
Red
Black
White
Low
pressure
sensor
(4)
(3)
(2)
(1)
X31A (Blue)
CHECK 2-1, 2-2