Troubleshooting
SiBE811001EB
183
CONVENI-PACK
8.4.12 Indoor Unit Thermistors Abnormality
Error Code
C4
,
C5
,
C9
Applicable
Models
All indoor models
Method of Error
Detection
Error detection is carried out by temperature detected by each thermistor.
Error Decision
Conditions
When the thermistor becomes disconnected or shorted while the unit is running.
Supposed
Causes
Wiring defect
Defective indoor unit thermistor
Defective indoor unit PCB
Troubleshooting
Note:
∗
1. Error code and thermistor
Refer to P.293.
Error code
Thermistor
Electric symbol
C4
Heat exchanger liquid pipe thermistor
R2T
C5
Heat exchanger gas pipe thermistor
R3T
C9
Suction air thermistor
R1T
NO
Is the operation
normal?
Remove the thermistor from the
indoor unit PCB, and then make
resistance measurement of the
thermistor using a multiple meter.
Is it normal?
5 k
Ω
to 90 k
Ω
Replace the indoor unit PCB.
YES
Normal (The error is caused by
faulty contact.)
YES
Replace the thermistor.
NO
Caution
Be sure to turn off the power switch before connecting or disconnecting connectors, or parts may be damaged.
Remove the thermistor (
∗
1) from the
indoor unit PCB, and then insert it
again.
CHECK 13
CHECK 13