SiBE811001EB
Troubleshooting
CONVENI-PACK
180
8.4.10 Capacity Determination Device Abnormality
Error Code
AJ
Applicable
Models
FXFQ, FXHQ, FXMQ
Method of Error
Detection
Capacity is determined according to resistance of the capacity setting adaptor and the memory
inside the IC memory on the indoor unit PCB, and whether the value is normal or abnormal is
determined.
Error Decision
Conditions
When the capacity code is not saved to the PCB, and the capacity setting adaptor is not
connected.
When a capacity that does not exist for that unit is set.
Supposed
Causes
The capacity setting adaptor was not installed.
Defective indoor unit PCB
Troubleshooting
Caution
Be sure to turn off the power switch before connecting or disconnecting connectors, or parts may be damaged.
NO
Replace the indoor unit PCB.
YES
NO
Replace the indoor unit PCB.
The indoor unit
PCB was
replaced with a
spare PCB.
The capacity setting
adaptor need to be
installed when
replacing the PCB.
YES
Install a capacity setting
adaptor.