Troubleshooting
SiBE811001EB
201
CONVENI-PACK
8.4.23 Electronic Expansion Valve Coil Abnormality
Error Code
E9
Applicable
Models
LRYEQ16AY1
Method of Error
Detection
Check disconnection of connector
To be detected based on continuity existence of electronic expansion valve coil
Error Decision
Conditions
No current is detected in the common (COM [+]) when power supply is ON.
Supposed
Causes
Disconnection of connectors for electronic expansion valve (Y1E~Y5E)
Defective electronic expansion valve coil
Defective outdoor unit main PCB or sub PCB