Troubleshooting
SiBE811001EB
283
CONVENI-PACK
8.5.23 System is not Set yet
Error Code
UF
Applicable
Models
LCBKQ3AV1
Method of Error
Detection
Error is detected by wiring check operation.
Error Decision
Conditions
The number of indoor units in terms of transmission is not corresponding to that of indoor units
that have made changes in temperature.
Supposed
Causes
Improper connection of transmission wiring between indoor-outdoor units and outdoor-
outdoor units
Failure to execute check operation
Defective booster unit PCB
Stop valve is not opened
Troubleshooting
LED Indications
First digit
l h k l h h l
Second digit
l k h l l l l
Is indoor-outdoor and
outdoor-outdoor unit
transmission wiring
normal?
Is the RESET button
pressed for 5
seconds?
YES
Replace the indoor unit PCB.
NO
After fixing the incorrect wiring,
press and hold the RESET
button on the master outdoor
unit PCB for 5 seconds.
∗
The unit will not run for up to
12 minutes.
NO
Replace the booster unit PCB.
YES
Caution
Be sure to turn off the power switch before connecting or disconnecting connectors, or parts may be damaged.