SiBE811001EB
Troubleshooting
CONVENI-PACK
224
8.4.41 Inverter Radiating Fin Temperature Rise Abnormality
Error Code
L4
Applicable
Models
LRYEQ16AY1
Method of Error
Detection
Fin temperature is detected by the thermistor of the radiation fin.
Error Decision
Conditions
When the temperature of the inverter radiation fin increases 84°C or more.
Supposed
Causes
Actuation of fin thermal (Actuates 84°C or more)
Defective inverter PCB
Defective radiation fin thermistor
Troubleshooting
Defective radiation from the
power unit
• Blocked air suction port
• Stained radiation fin
• High outdoor air temperature
YES
Replace the thermistor.
NO
Replace the compressor
inverter PCB.
YES
Continue the operation.
z
It is supposed that the
radiation fin temperature
became high due to some
field factors. In this
connection, check the
following points:
• Stained radiation fin
• Airflow obstructed with dirt
or foreign matters
• Damage to fan impellers
• Too high outdoor air
temperature
NO
Caution
Be sure to turn off the power switch before connecting or disconnecting connectors, or parts may be damaged.
The radiation fin of the
inverter PCB concerned
exceeded a temperature
of 84˚C.
Turn OFF the power supply, and then
make measurement of resistance of
the radiation fin thermistor.
NO
YES
Is the thermistor
resistance normal?
Connect and disconnect the connector
(X30A) for the radiation fin thermistor,
and then properly connect it.
Does the error recur
when the power supply
turns ON to start the
compressor?