SiBE811001EB
Troubleshooting
CONVENI-PACK
162
8.4
Troubleshooting by Indication on the Remote Controller
8.4.1 Error of External Protection Device
Error Code
A0
Applicable
Models
All indoor models
Method of Error
Detection
Detect open or short circuit between external input terminals in indoor unit
Error Decision
Conditions
When an open circuit occurs between external input terminals with the remote controller set to
"external ON/OFF terminal"
Supposed
Causes
Actuation of external protection device
Improper field setting
Defective indoor unit PCB
Troubleshooting
Caution
Be sure to turn off the power switch before connecting or disconnecting connectors, or parts may be damaged.
External protection
device is connected to
terminals T1 and T2 of
the indoor unit
terminal strip.
YES
YES
NO
NO
The setting
position is set to
“03”.
Check the setting state of the ON/OFF
input from outside by remote
controller.
Actuation of external protection
device.
Probe the cause of actuation of
the external protection device
and then take countermeasures
against it.
Change the setting position to
"01" or "02" .
Replace the indoor unit PCB.