manualshive.com logo in svg
background image

DAIKIN 

SPLIT SYSTEM 

MODELS 

INSTALLATION MANUAL 

Air Conditioner 

Floor Standing type

INDOOR 

FVFC

71

AV

1

6

FVFC

1

00AV

1

6

FVFC

1

40AV

1

6

OUTDOOR 

RZVF

71BS

V

1

6

RZVF

1

00

BS

V

1

6

RZMF

1

40

BS

V

1

6

Page No. 

Installation Manual I

DU.......... 01-23 

Installation Manual O

DU ......... 24-60 

R-32 Split Type Air Conditioner

CAREFULLY READ THESE INSTRUCTIONS BEFORE INSTALLATION.  

English 

Содержание FVFC71AV16

Страница 1: ...or Standing type INDOOR FVFC71AV16 FVFC100AV16 FVFC140AV16 OUTDOOR RZVF71BSV16 RZVF100BSV16 RZMF140BSV16 Page No Installation Manual IDU 01 23 Installation Manual ODU 24 60 R 32 Split Type Air Conditi...

Страница 2: ...CVR IMOM FS FVFC RZFC DAIKIN EN indd 2 CVR IMOM FS FVFC RZFC DAIKIN EN indd 2 5 14 2020 5 56 46 PM 5 14 2020 5 56 46 PM...

Страница 3: ...ELECTRICAL WIRING CONNECTION 13 6 REFRIGERANT PIPING WORK 14 ABOUT OPERATION 1 CONTROLLER PART NAMES AND FUNCTIONS 18 2 OPERATING INSTRUCTION 19 3 INDICATOR LIGHTS 20 4 TROUBLESHOOTING 21 5 OVERALL C...

Страница 4: ...I J K H L G Dimension Model A B C D E F G H I J K L 71A 514 254 1850 676 859 600 270 242 73 77 31 34 100 140A 514 254 1850 676 859 600 350 322 73 77 115 34 1 IMOM FS FVFC RZFC DAIKIN EN indd 2 1 IMOM...

Страница 5: ...ithstand the weight of the unit A foundation of insufficient strength may result in the equipment falling and causing injury Electrical work must be performed in accordance with relevant local and nat...

Страница 6: ...nsation Improper drain piping may result in indoor water leakage and property damage Tighten the flare nut according to specified method such as with a torque wrench If the flare nut is too tight it m...

Страница 7: ...r may drip Does the power supply voltage correspond to that shown on the name plate The unit may malfunction or the component burn out Are wiring and piping correct The unit may malfunction or the com...

Страница 8: ...unit or use in room where mineral oil oil vapour or oil steam exist this may cause plastic part to melt or deform as a result of excessive heat or chemical reaction When the unit is used in kitchen k...

Страница 9: ...s are secured and the base of the fan coil unit is leveled in both horizontal directions Figure B 50mm or more 50mm or more Please ensure that the following steps are taken The drain pipe slope shall...

Страница 10: ...you and 2 lift upward and out Refer Figure C Figure C M4 x 12 Screw Front Panel Grille stopper Intake grille 2 Install the indoor units Method 1 Fix the bracket with the attached screws to the top pa...

Страница 11: ...2 during installation Piping and Drain Hose Installation Detach the pipe retainer In case of left or right piping 1 Open the holes on the Right Left side panel Refer to Figure F 2 Pass refrigerant pip...

Страница 12: ...pipes and unit wiring through the hole on the bottom frame Figure G Bottom panel Insulation for fitting Pipe retainer Rear panel Knock out hole Drain hose inside the unit Fix using the cable tie Cut h...

Страница 13: ...k from the unit Therefore definitely insulate the hose in at least the below two places All hose in the room and inside the unit At connection between the unit s drain hose and building drain pipe 2 A...

Страница 14: ...eps below shall be followed 1 Confirm that the unit had been switched off before servicing the unit 2 Use screwdriver to unlock the screw on the intake grille 3 Install the intake grille and screw the...

Страница 15: ...nal for connecting wires to the power supply terminal block Connect the wires by matching to the indication on terminal block Refer to the wiring diagram attached on the unit Attach insulation sleeve...

Страница 16: ...of the flare Use refrigeration oil for R32 3 Use torque wrenches when tightening the flare nuts to prevent damage to the flare nuts and gas leakage CAUTION Align the centres of both flares and tighte...

Страница 17: ...are illegible shall be corrected refrigeration pipe or components are installed in a position where they are unlikely to be exposed to any substance which may corrode refrigerant containing components...

Страница 18: ...en charging is complete if not already Extreme care shall be taken not to overfill the refrigeration system Prior to recharging the system it shall be pressure tested with OFN The system shall be leak...

Страница 19: ...ll be available and in good working order Hoses shall be complete with leak free disconnect couplings and in good condition Before using the recovery machine check that it is in satisfactory working o...

Страница 20: ...6 FAN SPEED CONTROL BUTTON Press the button to active deactivate TURBO function Press the button to select fan speed High Medium Low of your choice 3 SWING BUTTON 7 ON OFF BUTTON Press the button to a...

Страница 21: ...limit is set to 20 C to 30 C 68 F to 86 F Pressing both keys simultaneously will toggle the temperature setting between C and F No temperature setting is allowed during FAN mode No set temp display T...

Страница 22: ...CH ERROR H6 COMPRESSOR FEEDBACK DETECTION ERROR H7 FAN MOTOR OVERLOADED OVERCURRENT SENSOR ABNORMAL H8 AC CURRENT SENSOR ERROR H9 OUTDOOR AIR THERMISTOR SHORT OPEN J1 PRESSURE SENSOR ERROR J3 COMPRESS...

Страница 23: ...rsist after all these verifications please contact the air conditioner unit installer 3 The air flow is too low The air filter is dirty The doors or windows are open The air suction and discharge are...

Страница 24: ...a vacuum cleaner or wash in lukewarm water below 40 C with a neutral cleaning detergent 2 Rinse the filter well and dry before placing it back onto the unit 3 Do not use gasoline volatile substances o...

Страница 25: ...g 2 4 12 Nakazaki Nishi Kita ku Osaka 530 8323 Japan Tokyo office JR Shinagawa East Bldg 2 18 1 Konan Minato ku Tokyo 108 0075 Japan http www daikin com global Lot 60334 Persiaran Bukit Rahman Putra 3...

Страница 26: ...CVR IMOM FS FVFC RZFC DAIKIN EN indd 2 CVR IMOM FS FVFC RZFC DAIKIN EN indd 2 5 14 2020 5 56 46 PM 5 14 2020 5 56 46 PM 24 RZVF71BSV16 RZVF71BSV16 24 26 26 27 30 30 33 34 35 38 39...

Страница 27: ...CVR IMOM FS FVFC RZFC DAIKIN EN indd 2 CVR IMOM FS FVFC RZFC DAIKIN EN indd 2 5 14 2020 5 56 46 PM 5 14 2020 5 56 46 PM 25 RZVF71BSV16...

Страница 28: ...CVR IMOM FS FVFC RZFC DAIKIN EN indd 2 CVR IMOM FS FVFC RZFC DAIKIN EN indd 2 5 14 2020 5 56 46 PM 5 14 2020 5 56 46 PM 26 RZVF71BSV16...

Страница 29: ...CVR IMOM FS FVFC RZFC DAIKIN EN indd 2 CVR IMOM FS FVFC RZFC DAIKIN EN indd 2 5 14 2020 5 56 46 PM 5 14 2020 5 56 46 PM 27...

Страница 30: ...CVR IMOM FS FVFC RZFC DAIKIN EN indd 2 CVR IMOM FS FVFC RZFC DAIKIN EN indd 2 5 14 2020 5 56 46 PM 5 14 2020 5 56 46 PM 28...

Страница 31: ...CVR IMOM FS FVFC RZFC DAIKIN EN indd 2 CVR IMOM FS FVFC RZFC DAIKIN EN indd 2 5 14 2020 5 56 46 PM 5 14 2020 5 56 46 PM 29...

Страница 32: ...CVR IMOM FS FVFC RZFC DAIKIN EN indd 2 CVR IMOM FS FVFC RZFC DAIKIN EN indd 2 5 14 2020 5 56 46 PM 5 14 2020 5 56 46 PM 30 RZVF71BSV16...

Страница 33: ...CVR IMOM FS FVFC RZFC DAIKIN EN indd 2 CVR IMOM FS FVFC RZFC DAIKIN EN indd 2 5 14 2020 5 56 46 PM 5 14 2020 5 56 46 PM 31 RZVF71BSV16...

Страница 34: ...CVR IMOM FS FVFC RZFC DAIKIN EN indd 2 CVR IMOM FS FVFC RZFC DAIKIN EN indd 2 5 14 2020 5 56 46 PM 5 14 2020 5 56 46 PM 32...

Страница 35: ...CVR IMOM FS FVFC RZFC DAIKIN EN indd 2 CVR IMOM FS FVFC RZFC DAIKIN EN indd 2 5 14 2020 5 56 46 PM 5 14 2020 5 56 46 PM 33...

Страница 36: ...CVR IMOM FS FVFC RZFC DAIKIN EN indd 2 CVR IMOM FS FVFC RZFC DAIKIN EN indd 2 5 14 2020 5 56 46 PM 5 14 2020 5 56 46 PM 34 RZVF71BSV16 RZVF71BSV16...

Страница 37: ...CVR IMOM FS FVFC RZFC DAIKIN EN indd 2 CVR IMOM FS FVFC RZFC DAIKIN EN indd 2 5 14 2020 5 56 46 PM 5 14 2020 5 56 46 PM 35...

Страница 38: ...CVR IMOM FS FVFC RZFC DAIKIN EN indd 2 CVR IMOM FS FVFC RZFC DAIKIN EN indd 2 5 14 2020 5 56 46 PM 5 14 2020 5 56 46 PM 36 RZVF71BSV16 RZVF71BSV16...

Страница 39: ...CVR IMOM FS FVFC RZFC DAIKIN EN indd 2 CVR IMOM FS FVFC RZFC DAIKIN EN indd 2 5 14 2020 5 56 46 PM 5 14 2020 5 56 46 PM 37 RZVF71BSV16 RZVF71BSV16...

Страница 40: ...CVR IMOM FS FVFC RZFC DAIKIN EN indd 2 CVR IMOM FS FVFC RZFC DAIKIN EN indd 2 5 14 2020 5 56 46 PM 5 14 2020 5 56 46 PM 38...

Страница 41: ...CVR IMOM FS FVFC RZFC DAIKIN EN indd 3 CVR IMOM FS FVFC RZFC DAIKIN EN indd 3 5 14 2020 5 56 46 PM 5 14 2020 5 56 46 PM 39...

Страница 42: ...40 RZVF100BSV16 RZMF140BSV16 RZVF100BSV16 Outdoor Unit High Low 4 15 3 30 UNPACKING PACKING INSTRUCTION OF OUTDOOR UNIT RZMF140BSV16 Design Pressure...

Страница 43: ...41...

Страница 44: ...42...

Страница 45: ...43...

Страница 46: ...44...

Страница 47: ...45...

Страница 48: ...46...

Страница 49: ...47 RZVF100BSV16 RZMF140BSV16 RZVF100BSV16 RZMF140BSV16...

Страница 50: ...48...

Страница 51: ...49...

Страница 52: ...50 RZVF100BSV16 RZVF100BSV16 RZMF140BSV16 RZMF140BSV16...

Страница 53: ...51 3...

Страница 54: ...52 RZVF100BSV16 RZMF140BSV16...

Страница 55: ...53 RZVF100BSV16 RZMF140BSV16 RZVF100BSV16 RZMF140BSV16 V V V...

Страница 56: ...54...

Страница 57: ...will take place for about 3 to 5 minutes Thereafter it will change to heating operation but this is not abnormal In this case the remote controller display will continue to display heating operation T...

Страница 58: ...56 RZVF100BSV16 RZMF140BSV16...

Страница 59: ...57...

Страница 60: ...58 RZVF100BSV16 RZMF140BSV16...

Страница 61: ...kid d with EPS by pulling the unit up then remove the polythene product cover by pulling it up 14 Unpacking Packing of the Outdoor Unit 14 1 Unpacking Remove the Top corrugated cardboard sheet with EP...

Страница 62: ...unit as shown in figure Fix the straps a on the unit with help of strap fixing machine f as shown in figure Use marked reference for placing straps a b c Strap Starp Cutter Top corrugated cardboard s...

Страница 63: ......

Страница 64: ...DAIKIN AIRCONDITIONING IND A PVT LTD 12th Floor Building No 9 Tower A DLF Cyber City DLF Phase Ill Gurgaon 122002 Haryana India Tel 91 0124 4555444 Fax 91 0124 4555333 3P754599 1...

Отзывы: