Tab.78 List of temporary error codes
Error
code
Message
Description
H00.17
DHW sensor Closed
Domestic Hot Water tank temperature sensor is either shorted or measures a
temperature above range
Check the wiring between the central unit PCB and the sensor.
Check that the sensor has been fitted properly.
Check the Ohmic value of the sensor.
Replace the sensor if necessary.
H00.32
TOutside Open
Outside temperature sensor is either removed or measures a temperature below range
Check the wiring between the central unit PCB and the sensor.
Check that the sensor has been fitted properly.
Check the Ohmic value of the sensor.
Replace the sensor if necessary.
H00.33
TOutside Closed
Outside temperature sensor is either shorted or measures a temperature above range
Check the wiring between the central unit PCB and the sensor.
Check that the sensor has been fitted properly.
Check the Ohmic value of the sensor.
Replace the sensor if necessary.
H00.47
HP flow sensor removed
or below range
Heat pump flow temperature sensor is either removed or measures a temperature
below range
Check the wiring between the central unit PCB and the sensor.
Check that the sensor has been fitted properly.
Check the Ohmic value of the sensor.
Replace the sensor if necessary.
H00.48
THp Flow Closed
Heat pump flow temperature sensor is either shorted or measures a temperature
above range
Check the wiring between the central unit PCB and the sensor.
Check that the sensor has been fitted properly.
Check the Ohmic value of the sensor.
Replace the sensor if necessary.
H00.51
THp Return Open
Heat pump return temperature sensor is either removed or measures a temperature
below range
H00.52
THp Return Closed
Heat pump return temperature sensor is either shorted or measures a temperature
above range
Check the wiring between the central unit PCB and the sensor.
Check that the sensor has been fitted properly.
Check the Ohmic value of the sensor.
Replace the sensor if necessary.
H00.57
T DHW Top Open
Domestic Hot Water top temperature sensor is either removed or measures a
temperature below range
Check the wiring between the central unit PCB and the sensor.
Check that the sensor has been fitted properly.
Check the Ohmic value of the sensor.
Replace the sensor if necessary.
H00.58
T DHW Top Closed
Domestic Hot Water top temperature sensor is either shorted or measures a
temperature above range
Check the wiring between the central unit PCB and the sensor.
Check that the sensor has been fitted properly.
Check the Ohmic value of the sensor.
Replace the sensor if necessary.
H02.00
Reset In Progress
Reset In Progress
H02.02
Wait Config Number
Waiting For Configuration Number
Waiting for configuration parameters to be entered
Configure CN1 / CN2 depending on the output of the outdoor unit installed (CNF
menu).
Central unit PCB replaced: heat pump not configured
11 Troubleshooting
7706696 - v04 - 11102018
AWHP-2 PBS-i
101
Содержание PBS-i WH2 Series
Страница 45: ...12 Appendix 7706698 v04 17102018 AWHP 2 PBS i 45 ...
Страница 46: ...12 Appendix 46 AWHP 2 PBS i 7706698 v04 17102018 ...
Страница 69: ...3 4 Electrical diagram Fig 12 MW 5000747 5 3 Technical specifications 7706696 v04 11102018 AWHP 2 PBS i 21 ...
Страница 154: ...12 Decommissioning and disposal 106 AWHP 2 PBS i 7706696 v04 11102018 ...
Страница 178: ...1 Spare parts 22 AWHP 2 PBS i 7706697 v04 11102018 ...