6. Configure the HP033 parameters according to the type of energy
meter installed. By default, the pulse weight is set to 1 Wh, the setting
range of the HP033 parameter goes from 0 (no metering) to 1000 Wh.
If the pulse weight is in kWh, use the following table.
Tab.56 If the pulse weight is given in kWh
Any numbers other than those stated in the table will not work.
Number of pulses per
kWh
Values to be configured for the HP033
parameter
1
1000
2
500
4
250
5
200
8
125
10
100
20
50
25
40
40
25
50
20
100
10
125
8
200
5
250
4
500
2
1000
1
7. Configure the HP034 and HP035 parameters.
Tab.57
Situation
Configuration
If a hydraulic back-up is
fitted
Set the HP034 and HP035 parameters to 0.
If an electrical back-up
is fitted
Set the HP034 and HP035 parameters according to the configuration of the electrical back-up stages
output.
9.3.7
Configuring a hydraulic back-up
Configure the back-up boiler according to its control panel. Set the installer
parameters.
1. Switch the boiler control system to 24h/24 comfort mode.
2. Heating set point temperature = Domestic hot water set point
tempe 5°C.
See
Boiler installation manual.
9.3.8
Configuring the hybrid operating mode of a hydraulic
back-up
Important
Hybrid operating mode is only available for appliances with a
hydraulic back-up.
The hybrid function consists of an automatic switch between the heat
pump and the boiler, according to the cost, the consumption or emission of
CO
2
of each heat generator.
9 Settings
80
AWHP-2 PBS-i
7706696 - v04 - 11102018
Содержание PBS-i WH2 Series
Страница 45: ...12 Appendix 7706698 v04 17102018 AWHP 2 PBS i 45 ...
Страница 46: ...12 Appendix 46 AWHP 2 PBS i 7706698 v04 17102018 ...
Страница 69: ...3 4 Electrical diagram Fig 12 MW 5000747 5 3 Technical specifications 7706696 v04 11102018 AWHP 2 PBS i 21 ...
Страница 154: ...12 Decommissioning and disposal 106 AWHP 2 PBS i 7706696 v04 11102018 ...
Страница 178: ...1 Spare parts 22 AWHP 2 PBS i 7706697 v04 11102018 ...