6.7.12 Connecting the power supply for the electrical back-up
1. Choose the total output of the electrical back-up according to the size
of the home and its energy performance. There are 2 output stages,
as shown in the following table:
Tab.32 Electrical back-up power supply
Back-up power supply
Output of the electrical back-up
Stage 1
Stage 2
Maximum output (Stage 1 +
Stage 2)
Single phase
2 kW
0 kW
2 kW
2 kW
2 kW
4 kW
2 kW
4 kW
6 kW
Three phase
3 kW
3 kW
6 kW
3 kW
6 kW
9 kW
2. Feed the electrical back-up power supply cable into the cable duct
reserved for the 230/400 V circuit cables.
3. Single-phase power supply:
3.1. Insert the bridge according to the output of the electrical back-
up, taking care to push it to the bottom of the connector.
3.2. Connect the electrical back-up power supply (press the button
to be able to insert the wire into the connector correctly and
secure it).
3.3. Insert the electrical back-up power cord into the cable way
located in the bottom part of the junction box.
Important
The bridge can be found in a bag inside the indoor module.
A
Bridge
B
Button
L1
Live
N
Neutral
Earth
Tab.33 Single-phase power supply
Maximum output
Bridge to be installed
2 kW
Do not install a bridge.
4 kW
A
6 kW
A
Fig.59
Single-phase power supply
2kW 230V~
L1 L2 L3 D3 N
4kW 230V~
6kW 230V~
L1 L2 L3 D3 N
L1 L2 L3 D3 N
MW-5000774-1
B
A
6 Installation
7706696 - v04 - 11102018
AWHP-2 PBS-i
53
Содержание PBS-i WH2 Series
Страница 45: ...12 Appendix 7706698 v04 17102018 AWHP 2 PBS i 45 ...
Страница 46: ...12 Appendix 46 AWHP 2 PBS i 7706698 v04 17102018 ...
Страница 69: ...3 4 Electrical diagram Fig 12 MW 5000747 5 3 Technical specifications 7706696 v04 11102018 AWHP 2 PBS i 21 ...
Страница 154: ...12 Decommissioning and disposal 106 AWHP 2 PBS i 7706696 v04 11102018 ...
Страница 178: ...1 Spare parts 22 AWHP 2 PBS i 7706697 v04 11102018 ...