ADV parameter
Description of the ADV advanced parameters
Factory setting
EHC–04
HP010
Minimum flow rate in heating mode
Can be set from 0 l/m to 90 l/m
5 for 4.5 kW
5 for 6 kW
8 for 8 kW
12 for 11 kW
12 for 16 kW
HP011
Minimum flow rate that triggers a warning message indicating that flow is going
low
Can be set from 0 l/m to 95 l/m
7 for 4.5 kW
7 for 6 kW
9 for 8 kW
14 for 11 kW
14 for 16 kW
HP030
Delay time for starting the next generator (backup stage) in central heating mode
Can be set from 0 Min to 600 Min
0
HP031
Delay time for stopping the next generator (backup stage) in central heating
mode
Can be set from 0 Min to 600 Min
0 = auto mode: use parameters HP047 to HP050
4
HP033
Pulse valency of the electrical meter
Can be set from 0 Wh to 1000 Wh
1
HP034
Capacity first electrical backup stage
Can be set from 0 kW to 10 kW
Value accepted when HP031 = 0
0
HP035
Capacity second electrical backup stage
Can be set from 0 kW to 10 kW
Value accepted when HP031 = 0
0
HP036
Rate of glycol added in the installation
0 =0% glycol
1 =20% glycol
2 =30% glycol
3 =40% glycol
0
HP047
Maximum time at maximum outside temperature to start back up in CH mode
when dynamic timer selected
Can be set from 1 to 10 minutes
Value accepted when HP031 = 0
8
HP048
Maximum time at maximum outside temperature to start back up in CH mode
when dynamic timer selected
Can be set from 0 to 60 minutes
Value accepted when HP031 = 0
30
HP049
Minimum outside temperature for dynamic timer when dynamic mode is selected
Can be set from -30 to 0 °C
Value accepted when HP031 = 0
-10
HP050
Maximum outside temperature for dynamic timer when dynamic mode is
selected
Can be set from -30 to +20 °C
Value accepted when HP031 = 0
15
HP051
Minimum operating temperature for the heat pump
Can be set from -20 to +5 °C
-15 °C for 4.5 kW
-15 °C for 6 kW
-20 °C for 8 kW
-20 °C for 11 kW
-20 °C for 16 kW
HP058
Enabling heat pump silent mode
0 =No
1 =Yes
Requires a specific option. Not available for AWHP 4.5 MR.
0
HP069
Heat pump flow speed setpoint depending on heat pump power configuration
Can be set from 0 to 100 l/min
12 for 4.5 kW
17 for 6 kW
23 for 8 kW
32 for 11 kW
46 for 16 kW
9 Settings
7706696 - v04 - 11102018
AWHP-2 PBS-i
75
Содержание PBS-i WH2 Series
Страница 45: ...12 Appendix 7706698 v04 17102018 AWHP 2 PBS i 45 ...
Страница 46: ...12 Appendix 46 AWHP 2 PBS i 7706698 v04 17102018 ...
Страница 69: ...3 4 Electrical diagram Fig 12 MW 5000747 5 3 Technical specifications 7706696 v04 11102018 AWHP 2 PBS i 21 ...
Страница 154: ...12 Decommissioning and disposal 106 AWHP 2 PBS i 7706696 v04 11102018 ...
Страница 178: ...1 Spare parts 22 AWHP 2 PBS i 7706697 v04 11102018 ...