Parameter Descriptions 7-23
MN766
Block Title
Parameter (Number)
Selection (Value)
Parameter Name and Description
PROCESS
CONTROL
(Continued)
PROC FEEDBACK
(2603)
Preset Value: 0
Range: 0 - 10
None (0)
No feedback assigned.
Setpoint Cmd (1)
Setpoint command value used for feedback.
Loc Speed Ref (2)
Local speed reference used for feedback.
Analog In1 (3)
Analog Input 1 signal used for feedback.
Analog In2 (4)
Analog Input 2 signal used for feedback.
Network (5)
Network value used for feedback.
Composite Ref (6)
Output of Composite Ref signal used for feedback.
Opt1 Ana In1 (7)
Option 1, Analog Input 1 used for feedback.
Opt1 Ana In2 (8)
Option 1, Analog Input 2 used for feedback.
Opt2 Ana In1 (9)
Option 2, Analog Input 1 used for feedback.
Opt2 Ana In2 (10)
Option 2, Analog Input 2 used for feedback.
Sets the type of signal used for the process feedback signal.
SETPOINT SOURCE
(2604)
Preset Value: 0
Range: 0 - 10
None (0)
Source of Process Loop Setpoint is not defi ned.
Setpoint Cmd (1)
Setpoint command value used for Setpoint.
Loc Speed Ref (2)
Local speed reference used for Setpoint.
Analog In1 (3)
Analog Input 1 signal used for Setpoint.
Analog In2 (4)
Analog Input 2 signal used for Setpoint.
Network (5)
Network value used for Setpoint.
Composite Ref (6)
Output of Composite Ref signal used for Setpoint.
Opt1 Ana In1 (7)
Option 1, Analog Input 1 used for Setpoint.
Opt1 Ana In2 (8)
Option 1, Analog Input 2 used for Setpoint.
Opt2 Ana In1 (9)
Option 2, Analog Input 1 used for Setpoint.
Opt2 Ana In2 (10)
Option 2, Analog Input 2 used for Setpoint.
Sets the source input signal type to which the process feedback will be
compared. If “Setpoint CMD” is selected, the fi xed value of the set point is
entered in the Setpoint Command parameter value.
SETPOINT COMMAND
(2605)
Preset Value: 0.0
Range: -100.0% to +100.0%
Sets the value as a percentage of the process feedback signal; the control
will try to maintain by adjusting motor speed. This is only used when the
Setpoint Source is a fi xed value “Setpoint CMD” under Setpoint Source.
PROC ERR TOL
(2606)
Preset Value: 10.0
Range: 0.0 - 100.0%
The band within which the Opto or Relay Output is active (turned ON)
indicating the process is within the desired range.
PROC PROP GAIN
(2607)
Preset Value: 1.0000
Range: 0.0000 - 1000.0000
Sets the PID loop proportional gain. Determines how much adjustment to
motor speed is due to process error.
PROC INTG GAIN
(2608)
Preset Value: 0.0000
Range: 0.0000 - 1000.0000
Sets the PID loop Integral gain. Determines how quickly the motor speed is
adjusted to correct long term error.
Table 7-2 Level 2 Parameter Block Defi nitions Continued
Содержание VS1SD
Страница 1: ...05 13 Installation Operating Manual MN766 VS1SD AC Servo Control...
Страница 12: ...2 2 General Information MN766...
Страница 16: ...3 4 Installing the Drive MN766...
Страница 108: ...7 34 Parameter Descriptions MN766...
Страница 114: ...8 6 Customizing Your Application MN766...
Страница 128: ...9 14 Troubleshooting MN766...
Страница 154: ...12 12 Monitor and RTC Description MN766...
Страница 188: ...E 2 Remote Keypad Mounting Template MN766...