Parameter Descriptions 7-3
MN766
Block Title
Parameter (Number)
Selection (Value)
Parameter Name and Description
KEYPAD
SETUP
STOP KEY
(1301)
Preset Value: 1
Range: 0 - 1
Off (0)
Keypad STOP key is not active.
On (1)
Allows keypad STOP key to initiate motor stop during remote or serial
operation. If active, pressing STOP selects Local mode and initiates the
stop command. Note: Pressing STOP key twice in rapid succession will
immediately terminate PWM to motor and disable the drive.
STOP MODE
(1302)
Preset Value: 0
Range: 0 - 1
Regen (0)
The voltage and frequency to the motor is reduced at a rate set by Decel
Time.
Coast (1)
Motor is turned off and allowed to coast to a stop.
Selects if the Stop command causes the motor to COAST to a stop or
REGEN to a stop.
RUN FORWARD
(1303)
Preset Value: 1
Range: 0 - 1
Off (0)
Disables FWD key in Local mode.
On (1)
Makes the keypad FWD key active in Local mode.
RUN REVERSE
(1304)
Preset Value: 1
Range: 0 - 1
Off (0)
Disables REV key in Local mode.
On (1)
Makes the keypad REV key active in Local mode.
SWITCH ON FLY
(1305)
(LOCAL/REMOTE KEY)
Preset Value: 0
Range: 0 - 1
Off (0)
Disables Switch on Fly.
On (1)
Allows switching between Local and Remote while Control is on.
LOCAL HOT START
(1306)
Preset Value: 0
Range: 0 - 1
Off (0)
Disables the Stop input at J2-11 in the keypad operating mode.
On (1)
Enables the Stop input at J2-11 in the keypad operating mode.
SPEED INCREMENT
(1307)
Preset Value: 30
Range: 1 to 2500 RPM or 0.01 to 60 Hz
Sets the increment of speed change for each key press. (1-3600 RPM or
0-60 Hz)
INIT LOCAL SPEED
(1308)
Preset Value: 0
Range: 0 - 2
Zero Speed (0)
Initializes local speed to 0 RPM on Power Up.
Last Speed (1)
Initializes local speed to last speed on Power Up.
Set Speed (2)
Initializes local speed to “Set Speed” (P1309) on Power Up.
SET SPEED
(1309)
Preset Value: 30
Range: 0 - MAX Speed RPM
At power up, initializes the local speed to this preset value if “Init Local
Speed” = Set Speed.
PARAMS TO KEYPAD
(1310)
Preset Value: 0
Range: 0 - 1
No (0)
No action.
Yes (1)
Transfers the parameter settings stored in the control memory (fl ash) to
keypad memory.
Table 7-1 Level 1 Parameter Block Defi nitions Continued
Содержание VS1SD
Страница 1: ...05 13 Installation Operating Manual MN766 VS1SD AC Servo Control...
Страница 12: ...2 2 General Information MN766...
Страница 16: ...3 4 Installing the Drive MN766...
Страница 108: ...7 34 Parameter Descriptions MN766...
Страница 114: ...8 6 Customizing Your Application MN766...
Страница 128: ...9 14 Troubleshooting MN766...
Страница 154: ...12 12 Monitor and RTC Description MN766...
Страница 188: ...E 2 Remote Keypad Mounting Template MN766...