Control Wiring 5-17
MN766
5.5.13 Profi le Run
Provides a speed profi le consisting of seven segments to setup a cyclic operation or test cycle. The opto inputs can be
switches as shown in Figure 5-17 or logic signals from another device. Speed settings for Speed Curve 1 to Speed Curve 7
are Preset Speed 1 to Preset Speed 7. See level 3, Profi le Run block for more information.
Figure 5-17 Profi le Run Connection Diagram
User Analog Return
Analog Input 1
Analog Ref. Power +
1
2
3
4
5
6
7
J1
Analog Input 2+
Analog Input 2-
Analog Output 1
Analog Output 2
Enable
J2
Digital Output 1 + (Collector)
Digital Output 1 - (Emitter)
Digital Output 2 + (Collector)
Digital Output 2 - (Emitter)
See Figure 5-4 for
connection information.
Enable
External Trip
Digital Input 1
Digital Input 2
Digital Input 3
Digital Input 4
Digital Input 5
Digital Input 6
Digital Input 7
Digital Input 8
8
17
9
10
11
12
13
14
15
16
18
19
20
Reset
Forward Enable
Reverse Enable
Run
Cycle
See recommended tightening torques in Table A-2.
*
*Note: Remove factory jumper from J2-8 and J3-24 before connecting switch at J2-8.
J2-8
CLOSED allows normal operation.
OPEN disables the control and motor coasts to a stop.
J2-9
CLOSED to enable operation in the Forward direction.
OPEN to disable Forward operation (drive will decel to a stop if a Forward profi le run command is still present).
Reverse operation is still possible if J2-10 is closed.
J2-10
CLOSED to enable operation in the Reverse direction.
OPEN to disable Reverse operation (drive will decel to a stop if a Reverse profi le run command is still present).
Forward operation is still possible if J2-9 is closed.
J2-11
CLOSED runs the profi le for an indefi nite number of cycles. When the Level 3, Profi le Run, Number of Cycles
(P3001) cycle count is reached, the counter is reset and the mode restarts (continuous cycling).
Example: If P3001 = 5 the profi le runs 5 times, the counter is reset to zero, and will begin running 5 more cycles
immediately. As long as pin 11 is closed it will keep resetting the count to zero every time the number of cycles is
reached.
OPEN cycle mode is terminated when cycle count is reached.
J2-12
CLOSED uses Run Command and Cycle Command from J2-9, J2-10 and J2-11.
OPEN uses Commands from Keypad.
J2-13 Not
used.
J2-14 Not
used.
J2-15
CLOSED resets an alarm or fault.
OPEN normal operation.
J2-16
Optional External Trip input (not required). If used, you must set Level 2 Drive Protect block, External Trip to “ON”.
CLOSED allows normal operation.
OPEN causes an External Trip to be received by the control (when programmed to “ON”).
Содержание VS1SD
Страница 1: ...05 13 Installation Operating Manual MN766 VS1SD AC Servo Control...
Страница 12: ...2 2 General Information MN766...
Страница 16: ...3 4 Installing the Drive MN766...
Страница 108: ...7 34 Parameter Descriptions MN766...
Страница 114: ...8 6 Customizing Your Application MN766...
Страница 128: ...9 14 Troubleshooting MN766...
Страница 154: ...12 12 Monitor and RTC Description MN766...
Страница 188: ...E 2 Remote Keypad Mounting Template MN766...