5-14 Control Wiring
MN766
5.5.10 E-POT 2-Wire
Provides speed Increase and Decrease inputs to allow E-POT (Electronic Potentiometer) operation with 2 wire inputs. The
values of the Preset Speeds are set in the Level 1 Preset Speeds block, Preset Speed 1 or Preset Speed 2. The opto inputs
can be switches as shown in Figure 5-14 or logic signals from another device.
Figure 5-14 E-POT 2-Wire Connection Diagram
User Analog Return
Analog Input 1
Analog Ref. Power +
1
2
3
4
5
6
7
J1
Analog Input 2+
Analog Input 2-
Analog Output 1
Analog Output 2
Enable
J2
Digital Output 1 + (Collector)
Digital Output 1 - (Emitter)
Digital Output 2 + (Collector)
Digital Output 2 - (Emitter)
See Figure 5-4 for
connection information.
Enable
Forward Run
Reverse Run
Switch 1
Switch 2
Accel/Decel
Increase
External Trip
Decrease
Digital Input 1
Digital Input 2
Digital Input 3
Digital Input 4
Digital Input 5
Digital Input 6
Digital Input 7
Digital Input 8
8
17
9
10
11
12
13
14
15
16
18
19
20
See recommended tightening torques in Table A-2.
*
*Note: Remove factory jumper from J2-8 and J3-24 before connecting switch at J2-8.
J2-8
CLOSED allows normal control operation.
OPEN disables the control and the motor coasts to a stop.
J2-9
CLOSED starts motor operation in the Forward direction.
OPEN motor decels to stop.
J2-10
CLOSED starts motor operation in the Reverse direction.
OPEN motor decels to stop.
Note:
Closing both J2-9 and J2-10 at the same time will reset a fault.
J2-11
Selects Preset Speeds as defi ned in the Speed Select Table (Table 5-10).
J2-12
Selects Preset Speeds as defi ned in the Speed Select Table (Table 5-10).
J2-13
CLOSED selects ACC / DEC / S-ACC /S-DEC group 2.
OPEN selects ACC / DEC / S-ACC /S-DEC group 1.
J2-14
MOMENTARY CLOSED increases motor speed while contact is closed.
J2-15
MOMENTARY CLOSED decreases motor speed while contact is closed.
J2-16
Optional External Trip input (not required). If used, you must set Level 2 Drive Protect block, External Trip to “ON”.
CLOSED allows normal operation.
OPEN causes an External Trip to be received by the control (when programmed to “ON”).
Table 5-10 Speed Select Table
J2-11
J2-12
Command
OPEN
OPEN
Electronic Pot
CLOSED
OPEN
Level 1, Input Setup, Command Source (parameter P1402)
OPEN
CLOSED
Preset 1
CLOSED
CLOSED
Preset 2
Содержание VS1SD
Страница 1: ...05 13 Installation Operating Manual MN766 VS1SD AC Servo Control...
Страница 12: ...2 2 General Information MN766...
Страница 16: ...3 4 Installing the Drive MN766...
Страница 108: ...7 34 Parameter Descriptions MN766...
Страница 114: ...8 6 Customizing Your Application MN766...
Страница 128: ...9 14 Troubleshooting MN766...
Страница 154: ...12 12 Monitor and RTC Description MN766...
Страница 188: ...E 2 Remote Keypad Mounting Template MN766...