PLC Mode Description 10-9
MN766
10.6 PLC Mode as 15 Preset Speed Mode
This example shows how the PLC Mode creates the 15 Preset Speed Mode.
Initialization:
Parameter
Value
Comment
P1401
PLC
PLC operating mode selected
PLC Mode confi guration parameters:
Parameter
Number
Parameter Dec
Value
Byte 3 Condition
Byte 2 Logic
Byte 1 Condition
Byte 0 Action
P3401
050.000.000.020
Input 1 (50)
OR (0)
False (0)
Forward (20)
P3402
051.000.000.024
Input 2 (51)
OR (0)
False (0)
Reverse (21)
P3403
001.000.000.035
True (1)
OR (0)
False (0)
Presets/Analog (24)
P3404
052.000.000.025
Input 3 (52)
OR (0)
False (0)
Preset Tbl Bit 0 (25)
P3405
053.000.000.026
Input 4 (53)
OR (0)
False (0)
Preset Tbl Bit 1 (26)
P3406
054.000.000.027
Input 5 (54)
OR (0)
False (0)
Preset Tbl Bit 2 (27)
P3407
055.000.000.028
Input 6 (55)
OR (0)
False (0)
Preset Tbl Bit 3(28)
P3408
052.001.053.040
Input 3 (52)
AND (1)
Input 4 (53)
Variable A (40)
P3409
054.001.055.041
Input 5 (54)
AND (1)
Input 6 (55)
Variable B (41)
P3410
100.001.101.023
A (100)
AND (1)
B (101)
Reset (23)
P3411
056.000.000.022
Input 7 (56)
OR (0)
False (0)
Acc/Dec Group (22)
P3412
057.003.000.019
Input 8 (57)
NOR (3)
False (0)
Fault (19)
User Analog Return
Analog Input 1
Analog Ref. Power +
1
2
3
4
5
6
7
J1
Analog Input 2+
Analog Input 2-
Analog Output 1
Analog Output 2
Enable
J2
Digital Output 1 + (Collector)
Digital Output 1 - (Emitter)
Digital Output 2 + (Collector)
Digital Output 2 - (Emitter)
Enable
Forward Run
Reverse Run
Switch 1
Switch 2
Switch 3
Switch 4
External Trip
Accel/Decel
Digital Input 1
Digital Input 2
Digital Input 3
Digital Input 4
Digital Input 5
Digital Input 6
Digital Input 7
Digital Input 8
8
17
9
10
11
12
13
14
15
16
18
19
20
*
See Figure 5-4 for
connection information.
*Note: Remove factory jumper from J2-8 and J3-24 before connecting switch at J2-8.
See recommended tightening torques in Table A-2.
The Parameter Dec Value column can be used when entering the PLC confi guration parameters at the keypad (parameters
are shown as decimal long values - byte3.byte2.byte1.byte0).
For this mode Enable is active.
Note that Preset Speed 1 is active so the Preset Speed Select Table Index need not be programmed since it automatically
follows action 24 (Presets/Analog).
Jog is enabled anytime input 3 or 4 is on while these same inputs set the direction for jog.
The Fault action is programmed to trigger whenever digital input 8 goes low.
Содержание VS1SD
Страница 1: ...05 13 Installation Operating Manual MN766 VS1SD AC Servo Control...
Страница 12: ...2 2 General Information MN766...
Страница 16: ...3 4 Installing the Drive MN766...
Страница 108: ...7 34 Parameter Descriptions MN766...
Страница 114: ...8 6 Customizing Your Application MN766...
Страница 128: ...9 14 Troubleshooting MN766...
Страница 154: ...12 12 Monitor and RTC Description MN766...
Страница 188: ...E 2 Remote Keypad Mounting Template MN766...