10-12 PLC Mode Description
MN766
Note that P3401 is programmed to set logical variable “A” before it is used since statements are executed in order from
P3401 through P3410.
Either input 5 or 6 enable jog and they also set jog direction as in P3407 and P3408.
Speed mode is active above 12 Hz but torque mode is active when less than 12Hz.
The PID becomes active above 12 Hz if input 4 is ON.
The PID becomes active at less than 12 Hz when input 4 is OFF.
The Fault action is programmed to trigger after a three second delay following digital input 8 going low.
Timer A is used to implement this action.
Normally P3410 continuously resets Timer A when digital input 8 is high.
If digital input 8 goes low then high in less than three seconds no fault action occurs since Timer A is reset before it has a
chance to timeout.
If digital input 8 goes low and stays low for at least 3 seconds then Timer A does timeout and a fault occurs.