High-Speed Input and Pulse Output Features
3–50
High-speed Input and Pulse Output Features
Recall that V7633 is the HSIO Mode Select register. Refer to the diagram below. Use
BCD 50 in the lower byte of V7633 to select the High-Speed Counter Mode. The
DL05 does not use bits 8 - 15 in V7633.
0
15 14 13 12
Memory Location V7633
11 10
1
2
3
4
5
6
7
8
9
Bits
0
0
0
0
0
0
1
0
1
0
0
HSIO Mode Setup (BCD)
0
0
0
0
50 = Pulse Catch Input
0
0
0
5
0
Bits 8 - 15 are not used
in V7633.
Choose the most convenient method of programming V7633 from the following:
S
Include load and out instructions in your ladder program
S
Direct
SOFT’s memory editor
S
Use the Handheld Programmer D2–HPP
We recommend using the first method above so that the HSIO setup becomes an
integral part of your application program. An example program later in this section
shows how to do this.
The configurable discrete input options for Pulse Catch Mode are listed in the table
below. Input X0 is the pulse input, and must have “0005” loaded into it configuration
register V7634. Inputs X1 and X2 can only be filtered inputs. Each input has its own
configuration register and filter time constant.
Input
Configuration
Register
Function
Hex Code
Required
X0
V7634
Pulse Catch Input
0005
X1
V7635
Filtered Input
xx06 (xx = filter time)
0 - 99 ms (BCD)
X2
V7636
Filtered Input
xx06 (xx = filter time)
0 - 99 ms (BCD)
Setup for Mode 50
X Input
Configuration
Содержание DL05
Страница 1: ...DL05 User Manual Automationdirect com ...
Страница 2: ...DL05 User Manual Automationdirect com ...
Страница 436: ...1B DL05 Error Codes In This Appendix Ċ Error Code Table ...
Страница 443: ...1C Instruction Execution Times In This Appendix Ċ Introduction Ċ Instruction Execution Times ...
Страница 459: ...1D Special Relays In This Appendix Ċ DL05 PLC Special Relays ...
Страница 464: ...1E DL05 Product Weights In This Appendix Ċ Product Weight Table ...
Страница 466: ...1F European Union Directives CE In This Appendix Ċ European Union EU Directives Ċ Basic EMC Installation Guidelines ...