PID Loop Operation
Maintenance
and T
roubleshooting
8–60
PID Loop Operation
Many applications do not require all 16 R/S steps. Use all zeros in the table for
unused steps. The R/S generator ends the profile when it finds ramp slope=0.
The individual bit definitions of the Ramp / Soak Table Flag (Addr+33) word is listed
in the following table.
Bit
Ramp / Soak Flag Bit Description
Read/Write
Bit=0
Bit=1
0
Start Ramp / Soak Profile
write
–
0
Õ
1 Start
1
Hold Ramp / Soak Profile
write
–
0
Õ
1 Hold
2
Resume Ramp / soak Profile
write
–
0
Õ
1
Resume
3
Jog Ramp / Soak Profile
write
–
0
Õ
1 Jog
4
Ramp / Soak Profile Complete
read
–
Complete
5
PV Input Ramp / Soak Deviation
read
Off
On
6
Ramp / Soak Profile in Hold
read
Off
On
7
Reserved
read
Off
On
8–15
Current Step in R/S Profile
read
decode as byte (hex)
The main enable control to permit
ramp/soak generation of the SP value is
accomplished with bit 11 in the PID Mode 1
Setting V+00 word, as shown to the right.
The other ramp/soak controls in V+33
shown in the table above will not operate
unless this bit=1 during the entire
ramp/soak process.
PID Mode 1 Setting V+00
0
1
3
4
5
6
7
8
9
10
11
12
13
14
15
2
Bit
Ramp/Soak
Generator Enable
The four main controls for the ramp/soak
generator are in bits 0 to 3 of the
ramp/soak settings word in the loop
parameter table.
Direct
SOFT32 controls
these bits directly from the ramp/soak
settings dialog. However, you must use
ladder logic to control these bits during
program execution. We recommend using
the bit-of-word instructions.
Ramp/Soak Settings V+33
0
1
3
4
5
6
7
8
9
10
11
12
13
14
15
2
Bit
Jog
Resume
Hold
Start
Ladder logic must set a control bit to a “1” to command the corresponding function.
When the loop controller reads the ramp/soak value, it automatically turns off the bit
for you. Therefore, a reset of the bit is not required, when the CPU is in Run Mode.
The example program rung to the right
shows how an external switch X0 can turn
on, and the PD contact uses the leading
edge to set the proper control bit to start
the ramp soak profile. This uses the Set
Bit-of-word instruction.
X0
SET
B2033.0
Start R/S Generator
Ramp/Soak
Table Flags
Ramp/Soak
Generator Enable
Ramp/Soak
Controls
Содержание DL05
Страница 1: ...DL05 User Manual Automationdirect com ...
Страница 2: ...DL05 User Manual Automationdirect com ...
Страница 436: ...1B DL05 Error Codes In This Appendix Ċ Error Code Table ...
Страница 443: ...1C Instruction Execution Times In This Appendix Ċ Introduction Ċ Instruction Execution Times ...
Страница 459: ...1D Special Relays In This Appendix Ċ DL05 PLC Special Relays ...
Страница 464: ...1E DL05 Product Weights In This Appendix Ċ Product Weight Table ...
Страница 466: ...1F European Union Directives CE In This Appendix Ċ European Union EU Directives Ċ Basic EMC Installation Guidelines ...