Drum Instruction
Programming
6–12
Drum Instruction Programming
Drum Instruction
The DL05 drum instructions may be programmed using
Direct
SOFT or for the
EDRUM instruction only you can use a handheld programmer (firmware version
v1.8 or later. This section covers entry using
Direct
SOFT for all instructions plus the
handheld mnemonics for the EDRUM instruction.
The Timed Drum with Discrete Outputs is the most basic of the DL05’s drum
instructions. It operates according to the principles covered on the previous pages.
Below is the instruction in chart form as displayed by
Direct
SOFT.
1
Kdddd
DRUM
CT
aaa
Step Preset K bb
0.01 sec/Count K cccc
Step #
Counts
2
Kdddd
3
Kdddd
4
Kdddd
5
Kdddd
6
Kdddd
7
Kdddd
8
Kdddd
9
Kdddd
10
Kdddd
11
Kdddd
12
Kdddd
13
Kdddd
14
Kdddd
15
Kdddd
16
Kdddd
Start
Reset
f f f f f f f f f f f f f f f f
f f f f f f f f f f f f f f f f
f f f f f f f f f f f f f f f f
f f f f f f f f f f f f f f f f
f f f f f f f f f f f f f f f f
f f f f f f f f f f f f f f f f
f f f f f f f f f f f f f f f f
f f f f f f f f f f f f f f f f
f f f f f f f f f f f f f f f f
f f f f f f f f f f f f f f f f
f f f f f f f f f f f f f f f f
f f f f f f f f f f f f f f f f
f f f f f f f f f f f f f f f f
f f f f f f f f f f f f f f f f
f f f f f f f f f f f f f f f f
f f f f f f f f f f f f f f f f
(Fffff)
(Fffff)
(Fffff)
(Fffff)
(Fffff)
(Fffff)
(Fffff)
(Fffff)
(Fffff)
(Fffff)
(Fffff)
(Fffff)
(Fffff)
(Fffff)
(Fffff)
(Fffff)
Discrete Output Assignment
Counter Number
Step Preset
Timebase
Control
Inputs
Step Number
Counts per Step
15
0
Output Pattern
f
= Off,
F
= On
The Timed Drum features 16 steps and 16 outputs. Step transitions occur only on a
timed basis, specified in counts per step. Unused steps must be programmed with
“counts per step” = 0 (this is the default entry). The discrete output points may be
individually assigned as X, Y, or C types, or may be left unused. The output pattern
may be edited graphically with
Direct
SOFT.
Whenever the Start input is energized, the drum’s timer is enabled. It stops when the
last step is complete, or when the Reset input is energized. The drum enters the
preset step chosen upon a CPU program-to-run mode transition, and whenever the
Reset input is energized.
Drum Parameters
Field
Data Types
Ranges
Counter Number
aaa
–
0 – 174
Preset Step
bb
K
1 – 16
Timer base
cccc
K
0 – 99.99 seconds
Counts per step
dddd
K
0 – 9999
Discrete Outputs
Fffff
X, Y, C
see page 4–28
Timed Drum with
Discrete Outputs
(DRUM)
Содержание DL05
Страница 1: ...DL05 User Manual Automationdirect com ...
Страница 2: ...DL05 User Manual Automationdirect com ...
Страница 436: ...1B DL05 Error Codes In This Appendix Ċ Error Code Table ...
Страница 443: ...1C Instruction Execution Times In This Appendix Ċ Introduction Ċ Instruction Execution Times ...
Страница 459: ...1D Special Relays In This Appendix Ċ DL05 PLC Special Relays ...
Страница 464: ...1E DL05 Product Weights In This Appendix Ċ Product Weight Table ...
Страница 466: ...1F European Union Directives CE In This Appendix Ċ European Union EU Directives Ċ Basic EMC Installation Guidelines ...