Installation, Wiring,
and Specifications
2–19
Installation, Wiring, and Specifications
The D0–05AR and the D0–05DR models feature relay outputs. Relays are best for
the following applications:
S
Loads that require higher currents than the solid-state DL05 outputs can
deliver
S
Cost-sensitive applications
S
Some output channels need isolation from other outputs (such as when
some loads require AC while others require DC)
Some applications in which NOT to use relays:
S
Loads that require currents under 10 mA
S
Loads which must be switched at high speed and duty cycle
Assuming relays are right for your application, we’re now ready to explore various
ways to wire relay outputs to the loads. Note that there are six normally-open SPST
relays available. They are organized with three relays per common. The figure below
shows the relays and the internal wiring of the PLC. Note that each group is isolated
from the other group of outputs.
Y0
Com
Y1
Y2
Y3
Y4
Com
Y5
In the circuit below, all loads use the same AC power supply which powers the DL05
PLC. In this example, all commons are connected together.
Output Point Wiring
Ground
Neutral
Line
Fuse or
Circuit
Breaker
In the circuit on the following page, loads for Y0 – Y2 use the same AC power supply
which powers the DL05 PLC. Loads for Y3 – Y5 use a separate DC supply. In this
example, the commons are separated according to which supply powers the
associated load.
Relay Output
Wiring Methods
Содержание DL05
Страница 1: ...DL05 User Manual Automationdirect com ...
Страница 2: ...DL05 User Manual Automationdirect com ...
Страница 436: ...1B DL05 Error Codes In This Appendix Ċ Error Code Table ...
Страница 443: ...1C Instruction Execution Times In This Appendix Ċ Introduction Ċ Instruction Execution Times ...
Страница 459: ...1D Special Relays In This Appendix Ċ DL05 PLC Special Relays ...
Страница 464: ...1E DL05 Product Weights In This Appendix Ċ Product Weight Table ...
Страница 466: ...1F European Union Directives CE In This Appendix Ċ European Union EU Directives Ċ Basic EMC Installation Guidelines ...