High-Speed Input and Pulse Output Features
3–46
High-speed Input and Pulse Output Features
Signal pulses at X0 must meet certain timing criteria to guarantee an interrupt will
result. Refer to the timing diagram below. The input characteristics of X0 are fixed (it
is not a programmable filtered input). The minimum pulse width is 0.1 mS. There
must be some delay before the next interrupt pulse arrives, such that the interrupt
period cannot be smaller than 0.5 mS.
Time
External
Interrupt
X0
0.1 mS minimum
0.5 mS minimum
When the timed interrupt is selected, the HSIO generates the interrupt to ladder
logic. There is no interrupt “pulse width” in this case, but the interrupt period can be
adjusted from 5 to 999 mS.
Time
Timed
Interrupt
5 mS to 999 mS
The configurable discrete input options for High-Speed Interrupt Mode are listed in
the table below. Input X0 is the external interrupt when “0004” is in V7634. If you
need a timed interrupt instead, then V7634 contains the interrupt time period, and
input X0 becomes a filtered input (uses X1’s filter time constant by default). Inputs
X1, and X2, can only be filtered inputs, having individual configuration registers and
filter time constants. However, X0 will have the same filter time constant as X1 when
the timed interrupt is selected.
Input
Configuration
Register
Function
Hex Code
Required
X0
V7634
External Interrupt
0004 (default)
Uses X1’s time
setting in V7635
Filtered Input (when
timed interrupt is in use)
xxx4, xxx = INT timebase
5 - 999 ms (BCD)
X1
V7635
Filtered Input
xx06 (xx = filter time)
0 - 99 ms (BCD)
X2
V7636
Filtered Input
xx06 (xx = filter time)
0 - 99 ms (BCD)
Interrupt O1 is also available as an interrupt. This interrupt is independent of the
HSIO features. Interrupt O1 uses an internal timer that is configured in V memory
location V7647. The interrupt period can be adjusted from 5 to 9999 mS. Once the
interrupt period is set and the interrupt is enabled in the program, the CPU will
continuously call the interrupt routine based on the time setting in V7647.
Input
Configuration
Register
Function
Hex Code
Required
–
V7647
High-Speed
Timed Interrupt
xxxx (xxxx = timer setting)
5 - 9999 mS (BCD)
External Interrupt
Timing Parameters
Timed Interrupt
Parameters
X Input / Timed
INT Configuration
Independent Timed
Interrupt
Содержание DL05
Страница 1: ...DL05 User Manual Automationdirect com ...
Страница 2: ...DL05 User Manual Automationdirect com ...
Страница 436: ...1B DL05 Error Codes In This Appendix Ċ Error Code Table ...
Страница 443: ...1C Instruction Execution Times In This Appendix Ċ Introduction Ċ Instruction Execution Times ...
Страница 459: ...1D Special Relays In This Appendix Ċ DL05 PLC Special Relays ...
Страница 464: ...1E DL05 Product Weights In This Appendix Ċ Product Weight Table ...
Страница 466: ...1F European Union Directives CE In This Appendix Ċ European Union EU Directives Ċ Basic EMC Installation Guidelines ...