Appendix A
Appendix F
EU Directives
F–8
European Union Directives
Due to slightly higher emissions radiated by the DC powered versions of the DL05, and
the differing emissions performance for different DC supply voltages, the following
stipulations must be met.
S
The PLC must be housed within a metallic enclosure with a minimum
amount of orifices.
S
The communication cable and all I/O cables must pass through suitable
ferrite beads which must be mounted within the enclosure. The I/O
cables can be bundled together and passed through the same ferrite.
Recommended ferrite beads and split cores are detailed below. These were used in
extensive EMC tests and found to successfully attenuate radiated emissions to a
high degree.
For I/O Bundle
Manufacturer
Mfg. Part No.
OD
mm
ID
mm
L
mm
1 Turn
L/25 MHz
W
1 Turn
L/100 MHz
W
2 Turn
L/25 MHz
W
2 Turn
L/100 MHz
W
RS Online
260–6795
17.5
9.5
28.5
153
210
649
632
Fair–Rite
2643665702
17.5
9.5
28.5
153
210
649
632
Wurth Elektronik
742 700 9
17.5
9.5
28.5
153
210
649
632
For Communication Cable
RS Online
222–4416
26.6
16.6
72
132
301
547
Fair–Rite
0444167281
26.6
10.7
16.6
72
132
301
547
Richco
MTFC 231114–T
26.6
10.7
16.6
72
132
301
547
DC Powered
Versions
Содержание DL05
Страница 1: ...DL05 User Manual Automationdirect com ...
Страница 2: ...DL05 User Manual Automationdirect com ...
Страница 436: ...1B DL05 Error Codes In This Appendix Ċ Error Code Table ...
Страница 443: ...1C Instruction Execution Times In This Appendix Ċ Introduction Ċ Instruction Execution Times ...
Страница 459: ...1D Special Relays In This Appendix Ċ DL05 PLC Special Relays ...
Страница 464: ...1E DL05 Product Weights In This Appendix Ċ Product Weight Table ...
Страница 466: ...1F European Union Directives CE In This Appendix Ċ European Union EU Directives Ċ Basic EMC Installation Guidelines ...