Appendix A
DL405 Error Codes
Appendix B
Error Codes
B–3
DL05 Error Codes
DL05 Error Code
Description
E360
HP PERIPHERAL
PORT TIME-OUT
The device connected to the peripheral port did not respond to the handheld
programmer communication request. Check to insure cabling is correct and
not defective. The peripheral device or handheld programmer could be
defective.
E4**
NO PROGRAM
A syntax error exists in the application program. The most common is a
missing END statement. Run AUX21 to determine which one of the E4**
series of errors is being flagged. SP52 will be on and the error code will be
stored in V7755.
E401
MISSING END
STATEMENT
All application programs must terminate with an END statement. Enter the
END statement in appropriate location in your program. SP52 will be on and
the error code will be stored in V7755.
E402
MISSING LBL
A MOVMC or LDLBL instruction was used without the appropriate label.
Refer to the Chapter 5 for details on these instructions. SP52 will be on and
the error code will be stored in V7755.
E403
MISSING RET
A subroutine in the program does not end with the RET instruction. SP52 will
be on and the error code will be stored in V7755.
E404
MISSING FOR
A NEXT instruction does not have the corresponding FOR instruction. SP52
will be on and the error code will be stored in V7755.
E405
MISSING NEXT
A FOR instruction does not have the corresponding NEXT instruction. SP52
will be on and the error code will be stored in V7755.
E406
MISSING IRT
An interrupt routine in the program does not end with the IRT instruction.
SP52 will be on and the error code will be stored in V7755.
E412
SBR/LBL>64
There is greater than 64 SBR or DLBL instructions in the program. This error
is also returned if there is greater than 2 INT instructions used in the program.
SP52 will be on and the error code will be stored in V7755.
E421
DUPLICATE STAGE
REFERENCE
Two or more SG or ISG labels exist in the application program with the same
number. A unique number must be allowed for each Stage and Initial Stage.
SP52 will be on and the error code will be stored in V7755.
E422
DUPLICATE LBL
REFERENCE
Two or more LBL instructions exist in the application program with the same
number. A unique number must be allowed for each and label. SP52 will be
on and the error code will be stored in V7755.
E423
NESTED LOOPS
Nested loops (programming one FOR/NEXT loop inside of another) are not
allowed. SP52 will be on and the error code will be stored in V7755.
E431
INVALID ISG/SG
ADDRESS
An ISG or SG instruction must not be placed after the end statement (such as
inside a subroutine). SP52 will be on and the error code will be stored in
V7755.
Содержание DL05
Страница 1: ...DL05 User Manual Automationdirect com ...
Страница 2: ...DL05 User Manual Automationdirect com ...
Страница 436: ...1B DL05 Error Codes In This Appendix Ċ Error Code Table ...
Страница 443: ...1C Instruction Execution Times In This Appendix Ċ Introduction Ċ Instruction Execution Times ...
Страница 459: ...1D Special Relays In This Appendix Ċ DL05 PLC Special Relays ...
Страница 464: ...1E DL05 Product Weights In This Appendix Ċ Product Weight Table ...
Страница 466: ...1F European Union Directives CE In This Appendix Ċ European Union EU Directives Ċ Basic EMC Installation Guidelines ...